Inspections for the day of: Wednesday, June 16, 2010.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00372 ELE-Aging Inspection6/16/20106/16/20106/18/2010 6:41:26 AM DONE
see final
ELE10-00194 ELE-Aging Inspection6/16/20106/16/20106/18/2010 6:39:59 AM DONE
suc
ELE09-02094 ELE-Aging Inspection6/16/20106/16/20106/18/2010 6:34:32 AM DONE
see final
ELE10-01286 Electrical Rough-In6/16/20106/16/20106/17/2010 9:41:47 AMPFAIL
steve Phone #: ###-#### called, left correction notice, NEC 210.52 shall add receptacles for 2' wall spacing at garage main landing, downstairs bar, living room divider,3110.4(D) sahll provide 1 1/4" protection for nm cable, 1120.26(F)(1) there shall be no foreign systems (piping) over dedicated space at panels, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-01305 Electrical Rough-In6/16/20106/16/20106/17/2010 8:00:52 AMPPART
Inspection requested from web by: Jon Gleason Phone #: ###-#### ri 3areas only ok
ELE08-01642 ELE-Aging Inspection6/16/20106/16/20106/17/2010 6:31:56 AM DONE
no activity, see doc expire
ELE08-01658 ELE-Aging Inspection6/16/20106/16/20106/17/2010 6:30:13 AM DONE
see final
ELE07-03910 ELE-Aging Inspection6/16/20106/16/20106/17/2010 6:26:02 AM DONE
see doc expire
ELE07-03817 ELE-Aging Inspection6/16/20106/16/20106/17/2010 6:24:42 AM DONE
see doc expire
ELE10-01275 Electrical Rough-In6/16/20106/16/20106/16/2010 3:47:46 PMPPASS
Please inpsect concrete covering grounding electrode Inspection requested from web by: Shaun Kirkman Phone #: ###-#### ok to backfill concreter encased electrode
ELE10-00989 Final6/16/20106/16/20106/16/2010 2:50:49 PMPPASS
dino - please call for access Phone #: ###-#### called, ok to final
ELE10-01328 Electrical Rough-In6/16/20106/16/20106/16/2010 1:55:39 PMPFAIL
Dustin Croft is our contact for the site. Inspection requested from web by: David Oliver Phone #: ###-#### called, left correction notice, NEC 334.23, shall protect cable within 6' of attic access, 210.52 shall provide receptacle in 2' wall by stairs, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 in combustible material, boxes shall be flush with finished surface, 210.52(E)(1) shall install receptacle at back of dwelling, BCC shall provide minimum 15"x20" access hole to jetted tub per instructions, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-01023 Final6/15/20106/16/20106/16/2010 1:02:16 PMPPASS
Richard-added a room-garage Phone #: ###-#### ok to final
ELE10-01318 Electrical Rough-In6/16/20106/16/20106/16/2010 12:18:58 PMPPASS
I have the key, I''ll be there between 10am and noon. Inspection requested from web by: Andy Derrick Phone #: ###-#### ric ok
ELE10-01318 Final6/16/20106/16/20106/16/2010 12:18:49 PMPPASS
I have the key, I''ll be there between 10am and noon. Inspection requested from web by: Andy Derrick Phone #: ###-#### ok to final
ELE10-01309 Conference6/15/20106/16/20106/16/2010 10:41:40 AMADONE
mitch Phone #: ###-#### reviewed service and work in progress, contractor will upgrade garage feeder and grounding
ELE10-01074 Electrical Rough-In6/15/20106/16/20106/16/2010 10:21:58 AMAPASS
Chad-Floor heat inspection Phone #: ###-#### ok to cover floor heat only, called, will work on service and call for inspection
ELE10-01075 Final6/15/20106/16/20106/16/2010 9:46:13 AMAFAIL
Inspection requested from web by: david bradshaw Phone #: ###-#### called, left message, NEC 408.4 shall make panel schedule fully explanatory, BCC shall finish or blank stage receptacles, firmly attach plug mold, finisha stage lighting,upstairs receptacles shall operate, install seismic wires for fixtures, NOTE: corrections shall be made in 5 working days or further action will be taken
ELE10-00893 Final6/16/20106/16/20106/16/2010 9:17:41 AMAPASS
GARAGE CODE 1968
THANKS, BILL Inspection requested from web by: Bob Glenn Phone #: ###-#### ok to final
ELE10-01311 Temporary Service6/15/20106/16/20106/16/2010 8:46:32 AMAPASS
THANKS Inspection requested from web by: Bob Glenn Phone #: ###-#### t/s u/g n ok
ELE10-01313 Electrical Rough-In6/15/20106/16/20106/16/2010 8:21:35 AMAPASS
ready for trench inspection Inspection requested from web by: gary batten Phone #: ###-#### ok to cover trench
ELE10-01312 Electrical Rough-In6/15/20106/16/20106/16/2010 8:21:03 AMAPART
ready inspection Inspection requested from web by: gary batten Phone #: ###-#### met contractor, will call for p/s later, grounding ok