Inspections for the day of: Tuesday, June 16, 2015.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01058 Final6/15/20156/16/20156/16/2015 3:51:23 PMPPASS
final on lighting retrofit exterior on building lights Phone #: ###-#### Inspection requested via web by Tim Dunlop Final ok
ELE15-01783 Final6/15/20156/16/20156/16/2015 3:37:54 PMPPASS
Call customer for access Stephanie ###-#### Phone #: ###-#### Inspection requested via web by jamie berg Final ok
ELE15-01783 Electrical Rough-In6/16/20156/16/20156/16/2015 3:37:39 PMPPASS
Call customer for access Stephanie ###-#### Phone #: ###-#### Inspection requested via web by jamie berg Rough in ok
ELE15-01782 Final6/15/20156/16/20156/16/2015 3:30:39 PMPPASS
Call customer for access Abel Florez ###-#### Phone #: ###-#### Inspection requested via web by jamie berg Final ok
ELE15-01782 Electrical Rough-In6/16/20156/16/20156/16/2015 3:30:08 PMPPASS
Call customer for access Abel Florez ###-#### Phone #: ###-#### Inspection requested via web by jamie berg AC rough in ok
ELE15-01798 Final6/16/20156/16/20156/16/2015 3:19:41 PMPPASS
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER Final ok
ELE15-01798 Electrical Rough-In6/16/20156/16/20156/16/2015 3:18:46 PMPPASS
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER Rough in ok
ELE15-01656 Electrical Rough-In6/16/20156/16/20156/16/2015 2:57:16 PMPPASS
Phone #: ###-#### Corrections made rough in ok cover
ELE15-00915 Final6/16/20156/16/20156/16/2015 2:36:01 PMPFAIL
Garage code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI 110.3- Master bath vanity receptacle not working.
210.12- Up bed outlet shall have AFCI protection.
410.16- Luminaire under stair shall clear shelf by min of 12"
ELE15-01787 Final6/15/20156/16/20156/16/2015 1:45:53 PMPPASS
We Went Out To Repair A Tripping Main Breaker And Found The bussing Was Burned From An Unbalanced Load. The Service Is Beyond repair And We Are Changing The Service. Firs Ting This morning. Please Call Me When You Are Headed Thais Way Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett Final ok
ELE15-01787 Permanent Service6/16/20156/16/20156/16/2015 1:44:47 PMPPASS
We Went Out To Repair A Tripping Main Breaker And Found The bussing Was Burned From An Unbalanced Load. The Service Is Beyond repair And We Are Changing The Service. Firs Ting This morning. Please Call Me When You Are Headed Thais Way Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett p/s o/h rec ok
ELE15-01795 Rough-In Permanent Service6/16/20156/16/20156/16/2015 1:24:51 PMPFAIL
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 300.4- NM calbe shall not be ran where it may be subject to physical damage. master bed firewall on clips.
334.30- NM cable shall be secured within 12" of smoke in masteer bed.
334.80- Where 2 or more NM cables are ran through bored holes without maintaining spacing derating calculations shall apply.
BCC- Firewall shall be clear for fire barrier. Wiring shall be relocated from behind studs in firewalls in master bed and garage.
ELE15-01794 Rough-In Permanent Service6/16/20156/16/20156/16/2015 1:14:10 PMPFAIL
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey
300.4- NM cable shall not be installed where it may be subject to physical damage.
334.30- MN cable shall be supported every 4 1/2' minimum. Fr. bed, furnace wire.
334.80- Where 2 or more NM cables ran through bored holes without maintaining spacing derating calculations shall apply.
BCC- Firewalls shall be clear for fire barrier. Wiring shall be relocated from behind studs in firewalls in master bed and garage.
ELE13-01023 ELE-Aging Inspection6/16/20156/16/20156/16/2015 11:15:20 AM CANC
too busy
ELE13-00354 ELE-Aging Inspection6/16/20156/16/20156/16/2015 11:10:43 AM DONE
Waiting on owner
ELE12-02995 ELE-Aging Inspection6/16/20156/16/20156/16/2015 11:09:44 AM DONE
Waiting on owner
ELE12-02434 ELE-Aging Inspection6/16/20156/16/20156/16/2015 11:05:43 AM DONE
Waiting on contractor
ELE15-01770 Electrical Rough-In6/16/20156/16/20156/16/2015 10:55:56 AMAPASS
Call Daniel if you have any questions. Thank you ###-#### Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
ELE15-01765 Final6/15/20156/16/20156/16/2015 10:13:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Thomas wilson Final ok
ELE15-01545 Rough-In Permanent Service6/16/20156/16/20156/16/2015 9:58:24 AMAPASS
Gary is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-01551 Conference6/15/20156/16/20156/16/2015 9:29:56 AMADONE
John Phone #: ###-#### discussed installation of a hot tub on back patio. Bonding ofmetal gutter with in 5 ' of waters edge, wire size, wiring path, disconnect location
ELE15-01747 Rough-In Permanent Service6/15/20156/16/20156/16/2015 8:57:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
ELE15-01776 Electrical Rough-In6/15/20156/16/20156/16/2015 8:26:08 AMAPASS
Underground Phone #: ###-#### Inspection requested via web by Eric Brown Hot tub going north side of existing pool check over head clearance of power lines, Under ground rough in ok cover