BLD15-01688
| FIRE-Final Inspection | 6/15/2015 | 6/16/2015 | 6/16/2015 2:11:53 PM | A | PASS |
|
|
Life fire safety inspection passed/complete
|
FIR15-00378
| INSP-Sprinkler Rough-in | 6/16/2015 | 6/16/2015 | 6/16/2015 1:58:14 PM | P | PART |
|
|
Notated area's approved for cover during this inspection in red on city approved plans. The second floor project is being split up to accomidate people, contractor will need to schedule rough to cover inspection for other area on 2nd floor.
|
BLD15-00946
| FIRE-Final Inspection | 6/16/2015 | 6/16/2015 | 6/16/2015 11:15:51 AM | P | FAIL |
|
|
Insulation/sheeting reating on fire sprinkler heads. Needs to be removed/repaired so as to not impede spray pattern of fire sprinkler head
|
BLD15-00944
| FIRE-Final Inspection | 6/16/2015 | 6/16/2015 | 6/16/2015 11:15:15 AM | P | FAIL |
|
|
Insulation/sheeting reating on fire sprinkler heads. Needs to be removed/repaired so as to not impede spray pattern of fire sprinkler heads
|
BLD15-00945
| FIRE-Final Inspection | 6/16/2015 | 6/16/2015 | 6/16/2015 10:51:29 AM | P | PASS |
|
|
Tenant shell inspected, fire sprinklers in this open shell space are satisfactory for coverage. Space will remain unoccupied, life fire safety passed/complete for shell tenant space.
|
BLD15-01719
| FIRE-Final Inspection | 6/15/2015 | 6/16/2015 | 6/16/2015 9:19:40 AM | A | PASS |
|
|
Life fire safety inspection passed/complete
|