BLD16-01492
| FIRE-Final Inspection | 6/16/2016 | 6/16/2016 | 6/16/2016 12:27:37 PM | P | CANC |
|
|
Jim Phone #: ###-####
|
BLD16-00926
| FIRE-Final Inspection | 6/16/2016 | 6/16/2016 | 6/16/2016 12:25:59 PM | P | PASS |
|
|
Life safety passed. Owner is going to make the pocket door in-operative instead of supply ADA hardware on it.
|
FIR16-00070
| INSP-Final Inspection | 6/14/2016 | 6/16/2016 | 6/16/2016 11:09:55 AM | A | FAIL |
|
|
Resubmit plans showing the three peaked sky lights with additional protection and show the two ceiling levels that surround the sky lights, show candella changes on the second floor, provide sync for all notification devices, provide additional notification in the basement lobby, provide the sample tubes and remote annunciators for the duct smoke detectors. The only devices tested today was the first floor lobby manual pull station, four fire/smoke damperson the first floor and the south duct detector on the second floor. All other devices need to be tested. I noted that the first floor manual pull station activated elevator recall which is not allowed in current code.
|
FIR16-00280
| INSP-Final Inspection | 6/15/2016 | 6/16/2016 | 6/16/2016 10:38:20 AM | A | CANC |
|
|
Scheduled with our alarm final. Mike Kroll Will be point of contact.(###-####) Phone #: ###-#### Inspection requested via web by Randy Knutson
|
BLD15-04501
| FIRE-Final Inspection | 6/15/2016 | 6/16/2016 | 6/16/2016 10:34:39 AM | A | CANC |
|
|
Need project related fire alarm permit addressed prior to a life safety inspection. I did note that atleast one fire extinguisher was expired.
|
BLD15-04361
| FIRE-Final Inspection | 6/15/2016 | 6/16/2016 | 6/16/2016 10:31:11 AM | A | CANC |
|
|
Need project related fire alarm permit addressed prior to a life safety inspection. I did note that atleast one fire extinguisher was expired.
|
FIR16-00356
| INSP-Final Inspection | 6/9/2016 | 6/16/2016 | 6/16/2016 10:04:13 AM | A | FAIL |
|
|
No city approved plans on site. No inspection was performed.
|
BLD16-01067
| FIRE-Final Inspection | 6/15/2016 | 6/16/2016 | 6/16/2016 8:03:23 AM | A | PASS |
|
|
life safety passed
|