Inspections for the day of: Thursday, June 16, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-01492 FIRE-Final Inspection6/16/20166/16/20166/16/2016 12:27:37 PMPCANC
Jim Phone #: ###-####
BLD16-00926 FIRE-Final Inspection6/16/20166/16/20166/16/2016 12:25:59 PMPPASS
Life safety passed. Owner is going to make the pocket door in-operative instead of supply ADA hardware on it.
FIR16-00070 INSP-Final Inspection6/14/20166/16/20166/16/2016 11:09:55 AMAFAIL
Resubmit plans showing the three peaked sky lights with additional protection and show the two ceiling levels that surround the sky lights, show candella changes on the second floor, provide sync for all notification devices, provide additional notification in the basement lobby, provide the sample tubes and remote annunciators for the duct smoke detectors. The only devices tested today was the first floor lobby manual pull station, four fire/smoke damperson the first floor and the south duct detector on the second floor. All other devices need to be tested. I noted that the first floor manual pull station activated elevator recall which is not allowed in current code.
FIR16-00280 INSP-Final Inspection6/15/20166/16/20166/16/2016 10:38:20 AMACANC
Scheduled with our alarm final. Mike Kroll Will be point of contact.(###-####) Phone #: ###-#### Inspection requested via web by Randy Knutson
BLD15-04501 FIRE-Final Inspection6/15/20166/16/20166/16/2016 10:34:39 AMACANC
Need project related fire alarm permit addressed prior to a life safety inspection. I did note that atleast one fire extinguisher was expired.
BLD15-04361 FIRE-Final Inspection6/15/20166/16/20166/16/2016 10:31:11 AMACANC
Need project related fire alarm permit addressed prior to a life safety inspection. I did note that atleast one fire extinguisher was expired.
FIR16-00356 INSP-Final Inspection6/9/20166/16/20166/16/2016 10:04:13 AMAFAIL
No city approved plans on site. No inspection was performed.
BLD16-01067 FIRE-Final Inspection6/15/20166/16/20166/16/2016 8:03:23 AMAPASS
life safety passed