Inspections for the day of: Friday, June 16, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01891 Final6/16/20176/16/20176/16/2017 2:39:52 PMPPASS
If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell Ok final
ELE17-01878 Permanent Service6/16/20176/16/20176/16/2017 2:36:13 PMPPASS
Roger Phone #: ###-#### p/s u/g rec ok. Customer needed a new 200a meter base. Existing wires from IDP a little short.
ELE17-01895 Conference6/16/20176/16/20176/16/2017 12:02:30 PMPDONE
Alan Phone #: ###-#### Discussed moving washer outlet up so GFI is accessable, and changing out box to allow for box fill. All grounds in boxes need tied together with 1 pigtail to ground switches and outlets. All metal boxes need ground screws.
ELE17-01853 Final6/16/20176/16/20176/16/2017 11:42:04 AMPPASS
Robert Phone #: ###-#### ok final. Breakered at 30a which is max fuse
ELE17-01729 Electrical Rough-In6/15/20176/16/20176/16/2017 11:23:23 AMPPASS
David Forbes ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Ok cover bar area up front and back 2 baths and storage area.
ELE17-01891 Permanent Service6/16/20176/16/20176/16/2017 11:07:07 AMPPASS
If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell p/s o/h rec ok. Homeowners wanted to label panel themselves. Notified contractor and mentioned that they needed to label panel due to possibility on incorrect labeling, which could be a liabilty in the future.
ELE17-01860 Electrical Rough-In6/16/20176/16/20176/16/2017 10:00:16 AMAPASS
Call Dylan ###-#### half hour prior for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Ok cover N wall. Existing wall was pushed back a couple of feet.
ELE17-00503 Final6/14/20176/16/20176/16/2017 9:39:51 AMAPASS
1919 CODE Phone #: ###-#### Inspection requested via web by Neal Rumsey Ok final
ELE17-01234 Final6/15/20176/16/20176/16/2017 9:06:37 AMAPASS
Phone #: ###-#### Inspection requested via web by John VanZandt Ok final
ELE17-01882 Electrical Rough-In6/15/20176/16/20176/16/2017 8:49:28 AMACANC
Pool bond for apron and motorized cover Phone #: ###-#### Inspection requested via web by TOM BICANDI Contractor wants to change to a Conference to discuss pool equipotential bonding
ELE17-01878 Conference6/15/20176/16/20176/16/2017 8:07:58 AMADONE
Roger-customer has Id Power coming out about 9 Phone #: ###-#### Talked to homeowner on phone. He is changing 100a to 200a panel. Meter is rated for 200a. He is changing GEC to #4 to ufer.