Inspections for the day of: Friday, June 16, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04354 FIRE-Final Inspection6/15/20176/16/20176/16/2017 11:33:47 AMAPASS
life safety passed
FIR17-00066 INSP-Final Inspection6/15/20176/16/20176/16/2017 11:33:07 AMAPASS
permit finaled. As-builts provided
FIR17-00161 INSP-Final Inspection6/15/20176/16/20176/16/2017 9:56:08 AMAPASS
Permit finaled
FIR16-00738 INSP-Conference6/15/20176/16/20176/16/2017 9:52:13 AMAPASS
See the city approved plans for more locations marked ok where tenting is approved and piping can be covered.
FIR17-00210 INSP-Final Inspection6/15/20176/16/20176/16/2017 8:44:16 AMAFAIL
Door failed to function upon activation of the smoke detectors
BLD16-04365 FIRE-Final Inspection6/14/20176/16/20176/16/2017 8:43:42 AMPPART
A temporary for life safety is given per documentation until the door in the adjoining space has been addressed
FIR17-00246 INSP-Sprinkler Rough-in/Hydro6/15/20176/16/20176/16/2017 7:31:59 AMAPART
Rough-in mostly passed. Piping is ok to cover. I noted sprinkler pendants are overspaced in two locations. The small room rule can not be used in the Storage Room and heads are 16' apart in the Conference Room. I also noted that two existing pendants at Elevator Lobby soffit are hanging below the ceiling and need adjustment.

Rich Phone #: ###-####