BLD16-04354
| FIRE-Final Inspection | 6/15/2017 | 6/16/2017 | 6/16/2017 11:33:47 AM | A | PASS |
|
|
life safety passed
|
FIR17-00066
| INSP-Final Inspection | 6/15/2017 | 6/16/2017 | 6/16/2017 11:33:07 AM | A | PASS |
|
|
permit finaled. As-builts provided
|
FIR17-00161
| INSP-Final Inspection | 6/15/2017 | 6/16/2017 | 6/16/2017 9:56:08 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00738
| INSP-Conference | 6/15/2017 | 6/16/2017 | 6/16/2017 9:52:13 AM | A | PASS |
|
|
See the city approved plans for more locations marked ok where tenting is approved and piping can be covered.
|
FIR17-00210
| INSP-Final Inspection | 6/15/2017 | 6/16/2017 | 6/16/2017 8:44:16 AM | A | FAIL |
|
|
Door failed to function upon activation of the smoke detectors
|
BLD16-04365
| FIRE-Final Inspection | 6/14/2017 | 6/16/2017 | 6/16/2017 8:43:42 AM | P | PART |
|
|
A temporary for life safety is given per documentation until the door in the adjoining space has been addressed
|
FIR17-00246
| INSP-Sprinkler Rough-in/Hydro | 6/15/2017 | 6/16/2017 | 6/16/2017 7:31:59 AM | A | PART |
|
|
Rough-in mostly passed. Piping is ok to cover. I noted sprinkler pendants are overspaced in two locations. The small room rule can not be used in the Storage Room and heads are 16' apart in the Conference Room. I also noted that two existing pendants at Elevator Lobby soffit are hanging below the ceiling and need adjustment.
Rich Phone #: ###-####
|