Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-02429 Final6/16/20206/16/20206/16/2020 2:20:04 PMPFAIL
flue test- installer will call- flue test failed- not holding pressure- installer said will fix and reschedule for friday at 830am to witness test- please reschedule
MEC20-02449 Pressure Test6/16/20206/16/20206/16/2020 2:01:55 PMPPASS
Pressure test
Gauge is at meter.
To fire pit. Phone #: ###-#### Inspection requested via web by Ed Ables- 20lb gas pass- ok to back fill- need shut off valve at firepit area gas line readily accessible within 6 feet of fire pit by final or install key way shutoff- call in final when ready
MEC20-02347 Final6/15/20206/16/20206/16/2020 1:50:15 PMPFAIL
Homeowner Richard Rector ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co locking caps ok- need protection post installed in front of furnace- need right size breaker installed in panel has 30 condenser max is 20- recall in when corrections made
MEC20-02352 Final6/10/20206/16/20206/16/2020 1:20:52 PMPNR
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney- will reschedule per conversation with Chad
MEC20-01387 Final6/16/20206/16/20206/16/2020 12:23:21 PMPPASS
Mechanical Gas Fireplace Final Inspection. Manual is in kitchen drawer right of stove. Garage Code: 3162 Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace final ok
MEC20-02429 Final6/15/20206/16/20206/16/2020 11:41:22 AMANR
Please call Matt if you have problems. Phone #: ###-#### Inspection requested via web by Matt Moser- rescheduled for pm inspection
MEC20-02100 DOC - Permit Finaled6/16/20206/16/20206/16/2020 11:25:21 AMAPASS
correction made- final ok- locking caps installed
MEC20-02423 Rough-in6/15/20206/16/20206/16/2020 10:52:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Shoecraft- fireplace R/I ok
MEC20-02423 Pressure Test6/16/20206/16/20206/16/2020 10:52:41 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Shoecraft- 20lb gas pass from furnace to fireplace
MEC20-02100 Final6/14/20206/16/20206/16/2020 10:09:32 AMAFAIL
Inspection requested via web by kevin Costa- furnace a/c coil co- need locking caps on a/c service ports- send pics for reinspect
MEC20-00820 Final6/15/20206/16/20206/16/2020 9:26:58 AMAFAIL
Field super: Daryl Thomas
gate code 1957 Phone #: ###-#### Inspection requested via web by Lisa Whitney- duct blast test needs completed- rest is good
MEC20-02295 Final6/10/20206/16/20206/16/2020 9:00:42 AMAPASS
Please call Heidi Hartnett prior to inspection. This is a rental and there is also a final inspection at her home. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
MEC20-02294 Final6/10/20206/16/20206/16/2020 8:55:26 AMAPASS
Please call Heidi Hartnett prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
MEC19-05125 Mec-Aging Inspection6/16/20206/16/20206/16/2020 8:02:32 AM CANC
should have been finaled on pressure test
MEC19-05125 DOC - Permit Finaled6/16/20206/16/20206/16/2020 8:02:03 AMAPASS
final ok