Inspections for the day of: Thursday, June 17, 1999.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE99-02137 INSP - Final6/17/19996/17/19996/18/1999 12:00:00 AMPFAIL
06/17/99 403 - George ###-#### NO GROUNDING CONDUCTOR CONNECTION TO ELECTRODE; SLB CONDUIT FITTING NOT OF CORRECT CU. IN. FOR SERVICE ENTRANCE CONDUCTO
ELE99-02139 INSP - Electrical Rough-In6/17/19996/17/19996/18/1999 12:00:00 AMPFAIL
06/17/99 403 - Alan ###-#### NEC: 370-16(B). BOX FILL. NEC: 370-17. NON METALIC SHEATHED CABLE LEN
ELE99-02090 INSP - Final6/16/19996/17/19996/17/1999 12:00:00 AMAPASS
###-####//groundwire INSPECTED BY JSCHMER.
ELE99-01319 INSP - Final6/15/19996/17/19996/17/1999 12:00:00 AMAFAIL
06/16/99 403 - Ed ###-#### NEC: 210-7(D)(3). NON-GROUNDING RECEPTICLES SHALL NOT BE REPLACED WITH
ELE99-01411 INSP - Final6/16/19996/17/19996/17/1999 12:00:00 AMAPASS
06/16/99 403 - ###-####//final SERVICE PANELS FOR PUMP EQUIPTMENT. OK
ELE99-01775 INSP - Electrical Rough-In6/17/19996/17/19996/17/1999 12:00:00 AMPCANC
06/17/99 403 - Fire alarm Dennis ###-#### WRONG INSPECTION REQUEST. WILL RESCHEDULE.
ELE99-01775 INSP - Final6/17/19996/17/19996/17/1999 12:00:00 AMPPASS
06/17/99 403 - Scheduled by Hello!. Contact phone is [8590536]. 2ND FLOOR OFFICES; TENANT IMPROVEMENT. OK
ELE99-01776 INSP - Electrical Rough-In6/17/19996/17/19996/17/1999 12:00:00 AMPCANC
06/17/99 403 - fire alarm Dennis ###-#### WRONG INSPECTION REQUEST.
ELE99-02031 INSP - Final6/17/19996/17/19996/17/1999 12:00:00 AMPPART
06/17/99 403 - ###-####//CALL B4 GOING 2 MEET U 4 ACCESS CONFERENCE ONLY; DISCUSSED GROUNDING FOR SERVICE PANEL.
ELE99-02055 INSP - Electrical Rough-In6/17/19996/17/19996/17/1999 12:00:00 AMPPART
06/17/99 403 - Brenda ###-#### OFFICE REMODEL; WALLS ELE R/I.
ELE99-00181 INSP - Final6/17/19996/17/19996/17/1999 12:00:00 AMPPASS
###-####//FINAL OK
ELE99-02138 INSP - Electrical Rough-In6/17/19996/17/19996/17/1999 12:00:00 AMPPASS
06/17/99 403 - Dawn ###-#### 1-ROOM REMODEL; WALL ELE R/I.