Inspections for the day of: Monday, June 17, 2002.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01545 Rough-In Permanent Service6/14/20026/17/20026/17/2002 12:00:00 AMANR
###-#### conference ok only complete wiring , and make up 210.52(A) spacing and needs fan box 6/17/2002 11:20:42 AM
ELE01-03349 Electrical Rough-In6/14/20026/17/20026/17/2002 12:00:00 AMAPART
DRRELL ###-#### PLEASE CALL SO HE CAN TELL YOU WHERE IT IS AT.. lights in retaining wall and pvc on back side ok 6/17/2002 11:56:38 AM
ELE02-01030 Final6/17/20026/17/20026/17/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 06/17/2002 at 08:17:17. Contact: ###-####. ok 6/17/2002 5:01:00 PM
ELE02-01546 Rough-In Permanent Service6/17/20026/17/20026/17/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 06/17/2002 at 09:21:51. Contact: ###-####. p/s only cor. posted called 300.4 11/4and nail plates see added p/s inspection 6/17/2002 5:51:46 PM
ELE02-01600 Permanent Service6/17/20026/17/20026/17/2002 12:00:00 AMPPASS
###-#### todd per ser

p/s u/g new ok 6/17/2002 3:49:35 PM
ELE02-01810 Temporary Service6/17/20026/17/20026/17/2002 12:00:00 AMPFAIL
t/p curtis- ###-#### cor. posted called 250.53 drive grd rod flush , 110.12(A) seal all unused openings 6/17/2002 2:33:18 PM
ELE02-01546 Permanent Service6/17/20026/17/20026/17/2002 12:00:00 AMPPASS

p/s u/g new ok