Inspections for the day of: Monday, June 17, 2002.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00314 FIRE-Final Inspection6/14/20026/17/20026/17/2002 12:00:00 AMAFAIL
cooking area insp- don- ###-####-fn rated door needs to meet 90 min; occupant load sign; extinguishing systems need MAU shutdown; duct detectors installed outside without protection (UL listing? for outside) 6/17/2002 5:10:15 PM
FIR02-00105 INSP-Alarm Testing6/12/20026/17/20026/17/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 06/12/2002 at 08:29:38. Contact: ###-####. need keys for knox box; elevator has primary recall only; 6/17/2002 5:10:58 PM