Inspections for the day of: Tuesday, June 17, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01612 FIRE-Final Inspection6/16/20036/17/20036/17/2003 12:00:00 AMAFAIL
austin; Phone #: ###-#### The inspection was for the fire sprinkler portion of the permit. Pendant sprinklers are overspace in numerous locations in the merchandizing areas.A sprinkler pendant needs to be provided in the closet or the ceiling is to be removed. Tire storage in the wharehouse to be less than 5'. Wood storage to be less than 10'. I could not verify a minimum .2 gpm over 130 sq. ft. density sprinkler design as the sticker on the riser is missing. I went over some life safety issues with the tenant 6/17/2003 2:02:30 PM
FIR03-00099 INSP-Supply line flush6/17/20036/17/20036/17/2003 12:00:00 AMAPASS
supply line flush is OK 6/17/2003 10:53:20 AM
FIR03-00110 INSP-Supply line flush6/17/20036/17/20036/17/2003 12:00:00 AMAPASS
supply line flush is ok 6/17/2003 10:50:15 AM
FIR03-00175 INSP-Supply line flush6/17/20036/17/20036/17/2003 12:00:00 AMAPASS
Underground supply line flush is OK 6/17/2003 9:08:28 AM
FIR03-00214 INSP-Sprinkler Rough-in/Hydro6/17/20036/17/20036/17/2003 12:00:00 AMPPASS
above ground hydro test is ok 6/17/2003 4:04:36 PM
FIR03-00175 INSP-Sprinkler Rough-in/Hydro6/17/20036/17/20036/17/2003 12:00:00 AMPPASS
center section piping ok to cover except for kitchen 6/17/2003 3:11:47 PM 6/17/2003 3:12:12 PM