FIR02-00359
| INSP-Final Inspection | 6/16/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 6/17/2004 8:04:24 AM
|
FIR04-00268
| INSP-Sprinkler Rough-in | 6/16/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | A | PART |
|
|
sprinkler piping is ok to cover in procedure areas (two) and the two restrooms. See approved plans for areas. 6/17/2004 2:01:46 PM
|
FIR03-00448
| INSP-Final Inspection | 6/16/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | A | FAIL |
|
|
provide correct canopies on all of the sprinkler pendants in the common areas on all floors. Per review note #3 lintels are to be provided above showers. No lintels have been provided. Sprinkler coverage is blocked by stub wall. Provide hydraulic test certificates. Provide additional heads for spare head cabinet (6 of each type) See note #42. 6/17/2004 3:10:36 PM
|
BLD03-00602
| FIRE-Final Inspection | 6/16/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | A | FAIL |
|
|
Chuck; Phone #: ###-#### Provide signage on doors, driveway and painting of access as discussed. Provide heat vent in trash shoot for heating of wet pipe sprinkler system. HVAC unit does not shut down upon alarm activation. 6/17/2004 3:12:15 PM
|
BLD02-00311
| FIRE-Final Inspection | 6/17/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled.
|
BLD04-00845
| FIRE-Final Inspection | 6/17/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | P | FAIL |
|
|
The existing fire alarm control panel is lacking a manual pull station and a smoke detector. Need to also final sprinkler permit 6/17/2004 3:59:01 PM
|
FIR04-00362
| INSP-Final Inspection | 6/17/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | P | FAIL |
|
|
Provide annual inspection for the fire sprinkler system 6/17/2004 3:15:12 PM
|
FIR03-00612
| INSP-Alarm Testing | 6/16/2004 | 6/17/2004 | 6/17/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm system finaled 6/17/2004 3:13:03 PM
|