FIR02-00388
| FIR-Aging Inspection | 6/17/2005 | 6/17/2005 | 6/20/2005 3:23:48 PM | | DONE |
|
|
Contacted Jeff Packam ###-#### at Treasure Valley in regards to this permit. Jeff said he will investigate and return phone call with a resolution.
|
FIR02-00466
| FIR-Aging Inspection | 6/17/2005 | 6/17/2005 | 6/20/2005 3:17:39 PM | | DONE |
|
|
Called Grinnell and spoke with Ronnie about the need to final this aging permit. He will contact Chris and take the necessary steps for a final.
|
FIR05-00104
| FIR-Aging Inspection | 6/17/2005 | 6/17/2005 | 6/17/2005 4:54:06 PM | | NR |
|
|
Permit has been recently issued, work is ongoing.
|
BLD04-00159
| FIRE-Final Inspection | 6/17/2005 | 6/17/2005 | 6/17/2005 4:27:46 PM | P | FAIL |
|
|
Install two emergency lights as shown in main area and reception area, label fire sprinkler backflow device and lock valves open, blank off lock at first set of vestibule doors, label fire lane curbing.
|
FIR05-00300
| INSP-Alarm Testing | 6/16/2005 | 6/17/2005 | 6/17/2005 3:13:57 PM | P | PART |
|
|
Two duct smoke detectors tested OK, horn/strobe locations and operation is satisfactory. Need to verify operation of preaction system under new programming, test smoke alarms, verify voltage drop.
|
BLD04-00313
| FIRE-Final Inspection | 6/17/2005 | 6/17/2005 | 6/17/2005 1:37:38 PM | P | PART |
|
|
Need correct verbage on sign above the main entry/exit, remaining life safety issues are acceptable.
|
FIR05-00085
| INSP-Final Inspection | 6/14/2005 | 6/17/2005 | 6/17/2005 1:32:42 PM | A | PASS |
|
|
Fire alarm finaled.
|
FIR04-00684
| INSP-Sprinkler Rough-in/Hydro | 6/16/2005 | 6/17/2005 | 6/17/2005 12:27:18 PM | P | PART |
|
|
Overhead rough-in basement area CPVC mains and branch lines are OK to cover.
|
FIR04-00684
| INSP-Supply line flush | 6/16/2005 | 6/17/2005 | 6/17/2005 12:25:11 PM | P | PART |
|
|
Underground fire supply line flush satisfactory.
|
FIR05-00155
| INSP-Conference | 6/16/2005 | 6/17/2005 | 6/17/2005 11:35:35 AM | A | DONE |
|
|
Discussed location of FDC to meet requirements of NFPA 13 8.16.2.4.6.
|
FIR05-00305
| INSP-Sprinkler Rough-in | 6/17/2005 | 6/17/2005 | 6/17/2005 11:07:56 AM | P | PART |
|
|
Overhead rough-in good for cover, final pending ceiling tile install and escutcheons.
|
FIR05-00277
| INSP-Sprinkler Rough-in | 6/16/2005 | 6/17/2005 | 6/17/2005 9:43:04 AM | A | FAIL |
|
|
Need re-submittals on core and shell work for approval of fir05-00045 prior to any approval of TI permits.
|
FIR05-00280
| INSP-Sprinkler Rough-in | 6/17/2005 | 6/17/2005 | 6/17/2005 12:00:00 AM | P | PART |
|
|
Overhead rough-in OK to cover, final pending installation of ceiling tile and escutcheons.
|
BLD04-00160
| FIRE-Final Inspection | 6/17/2005 | 6/17/2005 | 6/17/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled.
|