Inspections for the day of: Tuesday, June 17, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-03243 FIRE-Final Inspection6/17/20086/17/20086/17/2008 5:34:43 PMPFAIL
Provide exit discharge lighting as per the notes on the approved plans. Provide annual inspection tag for the fire extinguishers. Provide canopies for the sprinkler pendants.
BLD07-03246 FIRE-Final Inspection6/16/20086/17/20086/17/2008 5:33:15 PMPPASS
fire life safey passed
FIR08-00285 INSP-Final Inspection6/17/20086/17/20086/17/2008 5:31:56 PMPPASS
permit finaled
FIR08-00203 INSP-Sprinkler Rough-in/Hydro6/16/20086/17/20086/17/2008 2:24:38 PMPPART
The 24 hour air test was started at 9:45 with just over 40psi on the guage.
BLD08-00315 FIRE-Final Inspection6/17/20086/17/20086/17/2008 1:43:07 PMPPASS
Life safety passed
BLD08-00859 FIRE-Final Inspection6/17/20086/17/20086/17/2008 1:11:59 PMPPASS
LIfe safety passed.
BLD07-02226 FIRE-Final Inspection6/16/20086/17/20086/17/2008 1:07:50 PMAPART
A temporary occupancy was given until the fire dept access is paved. The contractor provided verification that the road could support 75,000lbs as per the IFC
BLD07-03029 FIRE-Final Inspection6/16/20086/17/20086/17/2008 11:06:42 AMAFAIL
The remote annunciator for the duct smoke detector was not functioning. The plastic sample tube needs to be removed from the duct smoke detector and then the detector needs tested. Provide the fire extinguisher as discussed. Provide approved hardware, single action on the south exterior exit door. Approved hardware needs to e provided on the main exit doors. Keyed hardware is ok on the main door if single action is provided on the tenant doors or the other way around.
BLD07-03030 FIRE-Final Inspection6/16/20086/17/20086/17/2008 10:14:51 AMAPASS
Life safety passed
BLD07-03028 FIRE-Final Inspection6/16/20086/17/20086/17/2008 9:50:26 AMAPASS
Life safety passed
FIR08-00419 INSP-Final Inspection6/16/20086/17/20086/17/2008 9:33:50 AMAPASS
Permit finaled
FIR08-00246 INSP-Final Inspection6/16/20086/17/20086/17/2008 8:58:43 AMAFAIL
The phone lines, flow switch and tamper switches tested ok. But a undefined signal came in for zone 7 which Brian is going to investigate it. We did not test the duct smoke detectors because the sample tubes extend out the back side of the duct work by up to 3' with the sample holes taped off with electrical tape. The first strobe that I looked at was overspaced off of the northwest wall. New walls are being built that are not shown on the plans and are effecting strobe placement. Due to the deficiencies listed above this test was a bust.
FIR08-00265 INSP-Final Inspection6/16/20086/17/20086/17/2008 7:55:10 AMAFAIL
The first audio/visual I looked at has not been set at the correct candella. Also when we activated the audio/visual devices the audio was not in sync or even in temporal. The visuals started flashing at different rates or not at all. Brian said it appears that the NAC panel has failed. Testing was stopped.