Inspections for the day of: Wednesday, June 17, 2009.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01061 Electrical Rough-In6/17/20096/17/20096/17/2009 4:25:00 PMPPART
Dan Phone #: ###-#### ok to cover under floor only, no esc this project
ELE09-00026 ELE-Aging Inspection6/17/20096/17/20096/17/2009 4:23:46 PM DONE
no activity, suc
ELE08-01021 ELE-Aging Inspection6/17/20096/17/20096/17/2009 3:18:08 PM DONE
no activity, suc
ELE08-00519 ELE-Aging Inspection6/17/20096/17/20096/17/2009 2:51:30 PM DONE
no activity, suc
ESC08-00518 General Inspection6/17/20096/17/20096/17/2009 2:30:08 PMPPASS
looked ok
ELE09-01063 Final6/17/20096/17/20096/17/2009 2:29:05 PMPPASS
ok to final, no esc this project
ELE09-01063 Electrical Rough-In6/17/20096/17/20096/17/2009 1:41:25 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Stuart Welton ric ok, no esc this project
ELE09-01064 Permanent Service6/17/20096/17/20096/17/2009 12:20:27 PMPPASS
John Phone #: ###-#### p/s o/h rec ok, no esc this project
ELE09-00874 Electrical Rough-In6/17/20096/17/20096/17/2009 11:13:45 AMAPASS
Call to meet in main hospital lobby
###-#### desk.
###-#### cell. Phone #: ###-#### Internet Inspection Request from: mark morris walls only ok to cover, no esc this project
ELE08-02560 Final6/17/20096/17/20096/17/2009 10:09:40 AMAPASS
please give me a call so that I can make sure someone is home to let you in. Thanks Shaun 941 6264 Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman met contractor, ok to final
ELE08-01360 Permanent Service6/16/20096/17/20096/17/2009 9:30:13 AMAPASS
warren Phone #: ###-#### p/s o/h rec ok, 2 meters, no esc this project
ELE09-01059 Rough-In Permanent Service6/16/20096/17/20096/17/2009 8:35:02 AMAPASS
Terry Phone #: ###-#### p/s o/h rec ok, no esc this project
ELE09-01051 Rough-In Permanent Service6/15/20096/17/20096/17/2009 8:07:14 AMAFAIL
space #17 service is ready, it is unoccupied, help yorself Phone #: ###-#### Internet Inspection Request from: gary batten called,left message, left correction notice, NEC 352.39(A) shall securely support pvc within 3' of termination, 342.30(A) shall securely support imc within 3' of termination, 312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed in electrical equipment, 334.15(B) nm cable shall be protected from physical damage, 408.4 shall provide circuit directory