Inspections for the day of: Thursday, June 17, 2010.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00218 INSP-Sprinkler Rough-in6/16/20106/17/20106/17/2010 11:21:01 AMAPASS
The sprinkler piping can be covered. A follow up inspection will be required to verify tenting prior to the blow in insulation.
FIR10-00194 INSP-Final Inspection6/16/20106/17/20106/17/2010 10:22:14 AMAFAIL
Relocate the two smoke detectors as clouded on the plans so that they do not exceed 15' from any one wall. Resubmit plans showing the correct candella used on the strobes. Resubmit plans that show the correct wire guage used for the notification circuits. Resubmit plans showing the three doors with the mag locks (access controled egress doors). The EOL voltage tested ok and two pull stations tested ok. Phone line troubles and battery troubles were received at the central station. Need to verify the items above and test the smoke detectors and heat detector.
FIR10-00243 INSP-Sprinkler Rough-in/Hydro6/16/20106/17/20106/17/2010 9:31:33 AMAPASS
Sprinler piping is ok cover. I noted that hanging obstructions in the corridor are being installed. They are also blocking the exit signs and emergency lights.
FIR07-00605 INSP-Final Inspection6/16/20106/17/20106/17/2010 9:17:53 AMAPASS
Permit finaled
FIR10-00241 INSP-Final Inspection6/17/20106/17/20106/17/2010 9:17:16 AMAPASS
Permit finaled