Inspections for the day of: Wednesday, June 17, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01086 ELE-Aging Inspection6/17/20156/17/20156/19/2015 7:41:48 AM CANC
Too busy
ELE13-00382 ELE-Aging Inspection6/17/20156/17/20156/17/2015 3:54:36 PM DONE
Still under construction
ELE15-01790 Permanent Service6/17/20156/17/20156/17/2015 3:24:06 PMPPASS
p/s u/g n ok 2 meters
ELE15-01790 Electrical Rough-In6/16/20156/17/20156/17/2015 3:21:46 PMPPASS
Inspection requested via web by Rowdy Monroe Both units rough in ok cover p/s u g n ok
ELE15-01819 Electrical Rough-In6/17/20156/17/20156/17/2015 2:50:57 PMPPASS
Ground // Richard Phone #: ###-#### (h)###-#### Conference and rough in because web sight for city caused delay in permitting. Only 2 circuits in back shop so 30 amp rated feed and disconnect in place. Underground and shop rough in ok cover
ELE15-01785 Electrical Rough-In6/17/20156/17/20156/17/2015 1:58:07 PMPFAIL
BCC- Informed contractor building permit required, clearances at peak and edges of roof
ELE15-01785 Permanent Service6/17/20156/17/20156/17/2015 1:48:20 PMPPASS
Ron ###-#### p/s u/g rec ok
ELE15-01800 Conference6/16/20156/17/20156/17/2015 1:20:24 PMADONE
We are requesting an electrical conference with our inspector for tomorrow 6/17/15 in the AM. Our onsite contact is Rich @ ###-####.
Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate By definiton Accessibility will still remain to junction box above HVAC equipment with new cover being provided in top or on back side of wire pull as per discussion with Daryl Degrange.
ELE15-01808 Electrical Rough-In6/17/20156/17/20156/17/2015 11:55:44 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews Up abed and covered patio rough in ok cover
ELE14-03133 Conference6/16/20156/17/20156/17/2015 11:08:50 AMADONE
Brad Phone #: ###-#### Discussed adding additional rooms to permit, multiwire branch circuits for when rearrange circuits in panel, totally enclosed lamps for storage areas
ELE15-01700 Electrical Rough-In6/16/20156/17/20156/17/2015 10:17:53 AMAPASS
Ron-ceiling Phone #: ###-#### Upper lid at truss bottom rough in ok cover
ELE15-00929 Final6/17/20156/17/20156/17/2015 9:31:54 AMAPASS
Gary is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
ELE15-01778 Temporary Service6/16/20156/17/20156/17/2015 8:58:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE15-01780 Temporary Service6/16/20156/17/20156/17/2015 8:52:13 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe 110.12(B)- Connections shall be tight. Loose connection meter lower left.