Inspections for the day of: Wednesday, June 17, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02792 ELE-Aging Inspection6/17/20156/17/20156/22/2015 9:43:59 AM DONE
ec says job has been finaled they will look into problem
ELE15-01795 Rough-In Permanent Service6/17/20156/17/20156/17/2015 3:49:59 PMPPASS
Inspection requested via web by Dan Hobdey rough-in ok cover p/s u/g n ok
ELE15-01794 Rough-In Permanent Service6/17/20156/17/20156/17/2015 3:49:16 PMPPASS
Inspection requested via web by Dan Hobdey rough-in ok p/s u/g n ok
ELE15-00431 Final6/17/20156/17/20156/17/2015 3:08:49 PMPFAIL
Rocky Phone #: ###-#### rooms 201-241-243-143-141 406.12 bath receptacles shall be tamper resistant finish paching sheetrock around boxes
GCE13-00081 GCE-Final6/17/20156/17/20156/17/2015 2:20:12 PMPPASS
Contractor ###-#### final ok
ELE15-01105 Final6/17/20156/17/20156/17/2015 1:51:58 PMPCANC
Please inspect floor heat also Phone #: ###-#### Inspection requested via web by TOM BICANDI needed rough-in for flr heat
ELE15-01105 Electrical Rough-In6/17/20156/17/20156/17/2015 1:47:45 PMPPASS
Please inspect floor heat also Phone #: ###-#### Inspection requested via web by TOM BICANDI floor heat 2nd floor bath ok cover
ELE15-00489 Final6/17/20156/17/20156/17/2015 1:23:39 PMPFAIL
Inspection requested via web by Terry Scott 210-8 all bath recepts shall have GFCI (downstairs bath) as well as recept in pantry
ELE15-01802 Electrical Rough-In6/16/20156/17/20156/17/2015 1:01:31 PMPPASS
Mike-as early PM as poss Phone #: ###-#### rough-in whole house remodel ok cover
GCE15-00054 GCE-Final6/16/20156/17/20156/17/2015 12:09:49 PMAFAIL
Zane ###-#### 210.8 all recepts in a comm kitchen shall be GFCI protected outlet for coffe maker
ELE15-01807 Rough-In Permanent Service6/16/20156/17/20156/17/2015 11:26:23 AMAFAIL
Chad Phone #: ###-#### 210-52 garage outlets shall serve no outside outlets 300.4 bored maintain 1 1/4 250.32 grounding electrode required for detached building
ELE15-01804 Permanent Service6/16/20156/17/20156/17/2015 10:05:17 AMACANC
Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan needed temp service
ELE15-01804 Temporary Service6/17/20156/17/20156/17/2015 10:04:47 AMPPASS
Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan t/s u/g n ok
ELE15-01810 Temporary Service6/16/20156/17/20156/17/2015 9:34:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-01726 Temporary Service6/16/20156/17/20156/17/2015 9:33:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-01620 Temporary Service6/16/20156/17/20156/17/2015 9:33:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-01786 Rough-In Permanent Service6/16/20156/17/20156/17/2015 8:54:59 AMAPASS
Lockbox 349. Thank you Phone #: ###-#### Inspection requested via web by Clay Morgan rough-in kitchen wall ok cover p/s o/h n rec ok