Inspections for the day of: Wednesday, June 17, 2020.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00722 Final6/17/20206/17/20206/17/2020 3:01:35 PMPPASS
Lockbox code 1987 on water spigot in front of garage. Inspection requested via web by Caleb Gaylord Corrections made final ok
ELE19-04644 Final6/17/20206/17/20206/17/2020 2:59:09 PMPPASS
Phone #: ###-#### Inspection requested via web by John VanZandt Contractor gave permision to enter. Unoccupied space but furniture being storred. Final ok
ELE20-01123 Final6/16/20206/17/20206/17/2020 2:25:09 PMPPART
Will be open, call Jerry with any questions ###-#### Phone #: ###-#### Inspection requested via web by Darryn Coburn Panel EP1 mislabeled, Redundent GFCI EP3 31 GFCI above small sink in coke room, Downsize breaker for small water heater above restrooms 2 pole 30 installed needs 2 pole 20. Partial final only ok
ELE20-01782 Final6/17/20206/17/20206/17/2020 1:52:44 PMPPASS
Please call Bruce when you arrive on site.

Thank you ; have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Corrections made final ok
ELE20-00281 Final6/17/20206/17/20206/17/2020 1:04:20 PMPCANC
Need inspection tomorrow P.M. for OK to energize. Phone #: ###-####
ELE20-00281 Permanent Service6/17/20206/17/20206/17/2020 1:03:59 PMPPASS
Need inspection tomorrow P.M. for OK to energize. Phone #: ###-#### p/s o/h rec ok
ELE19-04178 Electrical Rough-In6/17/20206/17/20206/17/2020 12:17:39 PMPPASS
Inspection is for the garage electrical rough in and feed, plus grounding. Also inspect main grounding corrections at the house. Thank you! Phone #: ###-#### Inspection requested via web by Philip Dixon underground to garage and ground rods in trench ok to cover ( Discussed lighting required at Detached garage man door. 210.70A2(2) At least one wall contralled light shall be installed at each detatched and attached gararge with man door at grade level.
ELE19-04505 Conference6/16/20206/17/20206/17/2020 11:07:57 AMAPASS
Please call Kris Kellner Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed Bonding of Generator and Main service gear. (4 wire ATS Nuetral break Bond at Generator, 3 wire ATS No Nuetral break No bond at generator.) Discussed Border tile install. No border tiles before inspection.
ELE20-00975 Electrical Rough-In6/16/20206/17/20206/17/2020 9:58:33 AMAPASS
Upstairs is ready, best access is from alley behind house Phone #: ###-#### Inspection requested via web by Troy Cobb Upstairs only ok to cover
ELE20-00281 Permanent Service6/16/20206/17/20206/17/2020 9:44:19 AMANR
Need inspection tomorrow A.M. for OK to energize. Phone #: ###-#### Inspection requested via web by Kelly Felin A.M disc. will be ready P.M
ELE20-01223 Final6/16/20206/17/20206/17/2020 9:42:48 AMAPASS
I will make sure it is open first thing Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
ELE20-00626 Electrical Rough-In6/16/20206/17/20206/17/2020 9:33:17 AMAPASS
Under slab rough-in east side. Thanks Phone #: ###-#### Inspection requested via web by Brad Hoots Event room underbground only ok to cover
ELE20-01992 Electrical Rough-In6/16/20206/17/20206/17/2020 8:22:50 AMAPASS
wall cover Phone #: ###-#### Inspection requested via web by Ryan Wake City stamped plans onsite Walls only ok to cover
ELE18-01747 ELE-Aging Inspection6/17/20206/17/20206/17/2020 6:40:28 AM PASS
Work completed under permit ELE20-00395. No work done under this permit. Final ok
ELE18-01747 Final6/17/20206/17/20206/17/2020 6:40:17 AMAPASS
Final ok see notes.