Inspections for the day of: Wednesday, June 17, 2020.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-02101 Rough-in6/17/20206/17/20206/17/2020 3:42:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Terek Worley- R/I ok- 5lb flue pass
MEC20-02458 Rough-in6/17/20206/17/20206/17/2020 3:25:06 PMPFAIL
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP
1- need approved man j onsite
2- need barbed fittings installed on pvc drains at unit and hook poly tubing to it
3- need 14x8 transfer in laundry room
4- need nail plates on all condensate with in 1.5 inches of framing

ok to insulate exterior walls only
MEC20-00098 Final6/16/20206/17/20206/17/2020 2:52:08 PMPFAIL
Final Inspection building 12 for towers 1, 2 and 3 - please contact shawn @ ###-#### Phone #: ###-#### Inspection requested via web by Amanda Casper
1- still need fire damper installation onsite and inspected- meet onsite with ladder
2- need locking caps on all A/Cs
3- K101-104 need wet switches install and all need wired for safety shutoff
4- K101 and 105 need lineset supported outside at a/c location- 5 need all dryer duct lengths permanently tagged all units
MEC15-02333 Final6/16/20206/17/20206/17/2020 2:47:35 PMPPART
Screened- Shawn Phone #: ###-####- need to fix T&P on water heater in basement- need to fix insulation to get off furnace flue- need pics sent of bath room and dryer vent 2nd floor- send pics of all items to final this out- talked with home owner onsite
MEC15-02333 Rough-in6/17/20206/17/20206/17/2020 2:44:29 PMPPASS
Screened- Shawn Phone #: ###-####- R/I ok all areas- ok to cover
MEC20-01715 Final6/15/20206/17/20206/17/2020 1:35:06 PMPPASS
Call George in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- furnace a/c coil co locking caps ok
MEC20-01195 Final6/16/20206/17/20206/17/2020 1:04:12 PMPPASS
AC: 4343 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
MEC20-02429 Final6/16/20206/17/20206/17/2020 11:59:24 AMAPASS
Inspection requested via web by Matt Moser- furnace a/c coil co locking caps ok- 5lb flue pass
MEC19-04530 Final6/16/20206/17/20206/17/2020 11:38:43 AMAPASS
Please call Ted at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda - final ok- card signed
MEC20-02379 Final6/16/20206/17/20206/17/2020 11:06:18 AMAFAIL
Please call the tenant Summer @ ###-#### when headed to the residence Phone #: ###-#### Inspection requested via web by Sarah Small- a/c coil co ok- need locking caps on a/c service ports- send pic for rerinspect
MEC20-02445 Final6/16/20206/17/20206/17/2020 10:36:15 AMAFAIL
Call ahead to Sherri @ ###-#### when headed to the residence Phone #: ###-#### Inspection requested via web by Sarah Small- a/c needs locking caps on a/c service ports- need to install wet switch on 2nd drain pan at coil location
MEC20-02390 Final6/16/20206/17/20206/17/2020 10:10:09 AMAFAIL
Homeowner Ryan Cardoza ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co locking caps ok- primary drain from coil to outside needs 1/4" per foor grade to outside has trap- send pic for reinspect
MEC20-02251 Final6/16/20206/17/20206/17/2020 9:43:51 AMAPASS
Please call Heidi on your way ###-####. Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil co locking caps ok
MEC20-02351 Final6/10/20206/17/20206/17/2020 9:16:50 AMAPASS
Robert *screened* Phone #: ###-####- 2 supply duct R/I ok
MEC20-02351 DOC - Permit Finaled6/17/20206/17/20206/17/2020 9:16:03 AMPPASS
Robert *screened* Phone #: ###-####- final ok 2 supplies
MEC20-02022 Final6/16/20206/17/20206/17/2020 9:00:05 AMAFAIL
Phone #: ###-#### Inspection requested via web by Sarah Small- a/c coil ok- need locking caps instaslled on a/c service ports- send pic for reinspect
MEC20-01221 Final6/16/20206/17/20206/17/2020 8:45:12 AMAPASS
the correct ac installed, please re-inspect
garage code 0425 or 3484 1225 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
MEC20-02153 Pressure Test6/16/20206/17/20206/17/2020 8:18:18 AMAPASS
Please call customer before heading out. Phone #: ###-#### Inspection requested via web by Mary Jane Schmidt- 20lb gas pass- ok to plug tee
MEC20-02153 DOC - Permit Finaled6/17/20206/17/20206/17/2020 8:17:52 AMAPASS
Please call customer before heading out. Phone #: ###-#### Inspection requested via web by Mary Jane Schmidt- gas piping range hood ducting ok- final ok
MEC19-03793 Mec-Aging Inspection6/17/20206/17/20206/17/2020 7:48:43 AM PASS
MEC19-03793 DOC - Permit Finaled6/17/20206/17/20206/17/2020 7:48:34 AMAPASS
final ok
MEC20-02352 Pressure Test6/17/20206/17/20206/17/2020 7:46:47 AMAPASS
5lb flue pass
MEC20-01462 Final6/16/20206/17/20206/16/2020 2:01:50 PMACANC
PROJECT MANAGER - KEVIN ###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt