Inspections for the day of: Wednesday, June 17, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03145 Electrical Rough-In6/17/20206/17/20206/17/2020 2:25:25 PMPPASS
3rd floor grid ceiling Phone #: ###-#### Inspection requested via web by Kevin Burke
3rd floor ceiling ok to cover
ELE20-02055 Temporary Service6/17/20206/17/20206/17/2020 2:25:02 PMPCANC
Phone #: ###-#### Inspection requested via web by Taras Shulga
ELE20-01727 Electrical Rough-In6/10/20206/17/20206/17/2020 2:12:38 PMPPASS
Boise City Street Light Pole Base Inspection. Phone #: ###-#### Inspection requested via web by Scott Campbell
Pole base ok to pour
ELE20-02045 Final6/16/20206/17/20206/17/2020 2:12:02 PMPPASS
Tenant should be home to get you access to panel, everything else is outside to inspect. Thanks Phone #: ###-#### Inspection requested via web by Jason Scott
Final ok
ELE20-02046 Final6/16/20206/17/20206/17/2020 2:11:42 PMPPASS
There is a lock box with a code 35789 on the front door to get you access to panel on the inside. Everything else is outside to inspect. Thanks Phone #: ###-#### Inspection requested via web by Jason Scott
Final ok
ELE20-00771 Final6/16/20206/17/20206/17/2020 12:04:05 PMAPART
Final on Units 119, 217, 218 and 219. Key is in lock box on site. Call for code if acceptable. Or call ahead of time and I can run over to unlock. Thanks, Tod Phone #: ###-#### Inspection requested via web by Tod Lane
Units ok to occupy
ELE20-01832 Final6/16/20206/17/20206/17/2020 10:22:26 AMAPASS
It is all outside. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Service change final ok
ELE20-02039 Final6/16/20206/17/20206/17/2020 10:06:49 AMAFAIL
Duane Oreilly is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
330.30(B) Sucuring and supporting of MC cable
210.8 insure GFCI protection of receptacles located within 6' of a sink
ELE20-01149 Rough-In Permanent Service6/16/20206/17/20206/17/2020 9:34:03 AMAPASS
We are installing a new service to facilitate a service change over, also iwe would like to add the outbuilding service the is out back of the home to the permit and have a service inspection on that as well! Thx, Steve PS.Mike should be on site, His number is ###-#### to feild any questions! Phone #: ###-#### Inspection requested via web by Steven Meredith
p/s u/g n ok
ELE19-04728 Final6/16/20206/17/20206/17/2020 9:15:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
Final ok
ELE20-01857 Electrical Rough-In6/16/20206/17/20206/17/2020 9:15:02 AMAPASS
Taylor Barton is the onsite contact - ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting
Verified U/L listing of Solar Array install-Approved plans on site