FIR19-00888
| INSP-Sprinkler Rough-in/Hydro | 6/17/2020 | 6/17/2020 | 6/17/2020 4:25:45 PM | P | DONE |
|
|
Hydrostatic test for underground supply witnessed via photo, no pressure loss observed by timed photos.
Jeff Chaney is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD20-01805
| FIRE-Final Inspection | 6/17/2020 | 6/17/2020 | 6/17/2020 3:08:51 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
screened - Geri Phone #: ###-####
|
FIR20-00176
| INSP-Final Inspection | 6/16/2020 | 6/17/2020 | 6/17/2020 3:02:20 PM | A | PASS |
|
|
Final fire sprinkler inspection for area of work is complete.
Please contact Adam Chitwood Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR20-00176
| INSP-Sprinkler Rough-in | 6/16/2020 | 6/17/2020 | 6/17/2020 3:01:17 PM | A | PASS |
|
|
Rough to cover inspection for area of work is complete, approved for cover.
Please contact Adam Chitwood Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR19-00623
| INSP-Sprinkler Rough-in/Hydro | 6/16/2020 | 6/17/2020 | 6/17/2020 2:30:36 PM | A | PART |
|
|
24 hour air test is complete with no visible loss of pressure at riser provided gauge.
24 hour air test - screened // Rick Phone #: ###-####
|
FIR20-00262
| INSP-Final Inspection | 6/12/2020 | 6/17/2020 | 6/17/2020 11:12:12 AM | A | CANC |
|
|
Inspection request cancelled per conversation with point of contact, during pre-test, sync issues were observed, inspection will be rescheduled after sync issue is resloved.
Please call 15-20 minutes prior to arrival. You will be meeting with technician Justin on site. Phone #: ###-#### Inspection requested via web by jason petty
|
FIR19-00914
| INSP-Supply line flush | 6/16/2020 | 6/17/2020 | 6/17/2020 10:16:52 AM | A | DONE |
|
|
Underground main line flush complete.
This inspection is scheduled for 9:00 AM. Jim Baker is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00888
| INSP-Supply line flush | 6/16/2020 | 6/17/2020 | 6/17/2020 9:36:05 AM | A | DONE |
|
|
Main line underground flush complete.