FIR03-00108
| FIR-Aging Inspection | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | | FAIL |
|
|
I left message for Mike Heath to contact me about the status of the project 6/20/2003 6:45:09 AM
|
FIR00-00419
| INSP-Sprinkler Rough-in | 6/17/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | A | FAIL |
|
|
kerry; Phone #: ###-#### Provide clamps on the FDC piping in the crawl space, remove tape from the sidewall heads in the second floor corridor, pendants are overspaced throughout the building. Sprinkler spacing is 149 sq. ft. max. Pendant sprinkler heads are less than one foot to supply registers thoughout the building as well 6/18/2003 11:50:26 AM
|
BLD03-00402
| FIRE-Final Inspection | 6/17/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | A | PASS |
|
|
###-#### don Fire life safety finaled. Per the owner the hvac system is an 1800 cfm unit, which means no automatic shutdown is required. A lock smith was on the way to remove the thumbturn on the main exit door. Structural inspector to please verify this 6/17/2003 3:34:01 PM
|
FIR03-00175
| INSP-Sprinkler Rough-in | 6/17/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | A | CANC |
|
|
doug; Phone #: ###-#### The sprinkler contractor called and cancelled the inspection due to another contractor removing the tenting insulation in the kitchen 6/18/2003 10:34:06 AM
|
FIR03-00181
| INSP-Sprinkler Rough-in/Hydro | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | PASS |
|
|
mike; Phone #: ###-#### Sprinkler rough in is OK 6/18/2003 3:50:37 PM
|
FIR03-00184
| INSP-Sprinkler Rough-in/Hydro | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | PASS |
|
|
mike; Phone #: ###-#### Sprinkler piping rough in is ok 6/18/2003 3:52:03 PM
|
FIR03-00317
| INSP-Conference | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | PASS |
|
|
Inspection was for supply line cover. The supply line is OK for cover 6/18/2003 3:48:31 PM
|
BLD03-01064
| FIRE-Final Inspection | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | FAIL |
|
|
###-#### Provide "Door to remain unlocked" sticker. Provide verification that the hvac unit is under 2000 cfm. Correct sprinkler deficiancies. Test emergency lights 6/18/2003 3:54:44 PM
|
FIR03-00110
| INSP-Final Inspection | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | PASS |
|
|
Supply line cover, flush and hydro is OK
|
FIR03-00099
| INSP-Final Inspection | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | PASS |
|
|
Supply line cover, flush and hydro is OK
|
FIR03-00291
| INSP-Final Inspection | 6/18/2003 | 6/18/2003 | 6/18/2003 12:00:00 AM | P | FAIL |
|
|
two drops off of a single 1" outlet in the same area. Needs to be only one drop in same area
|