Inspections for the day of: Wednesday, June 18, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00108 FIR-Aging Inspection6/18/20036/18/20036/18/2003 12:00:00 AM FAIL
I left message for Mike Heath to contact me about the status of the project 6/20/2003 6:45:09 AM
FIR00-00419 INSP-Sprinkler Rough-in6/17/20036/18/20036/18/2003 12:00:00 AMAFAIL
kerry; Phone #: ###-#### Provide clamps on the FDC piping in the crawl space, remove tape from the sidewall heads in the second floor corridor, pendants are overspaced throughout the building. Sprinkler spacing is 149 sq. ft. max. Pendant sprinkler heads are less than one foot to supply registers thoughout the building as well 6/18/2003 11:50:26 AM
BLD03-00402 FIRE-Final Inspection6/17/20036/18/20036/18/2003 12:00:00 AMAPASS
###-#### don Fire life safety finaled. Per the owner the hvac system is an 1800 cfm unit, which means no automatic shutdown is required. A lock smith was on the way to remove the thumbturn on the main exit door. Structural inspector to please verify this 6/17/2003 3:34:01 PM
FIR03-00175 INSP-Sprinkler Rough-in6/17/20036/18/20036/18/2003 12:00:00 AMACANC
doug; Phone #: ###-#### The sprinkler contractor called and cancelled the inspection due to another contractor removing the tenting insulation in the kitchen 6/18/2003 10:34:06 AM
FIR03-00181 INSP-Sprinkler Rough-in/Hydro6/18/20036/18/20036/18/2003 12:00:00 AMPPASS
mike; Phone #: ###-#### Sprinkler rough in is OK 6/18/2003 3:50:37 PM
FIR03-00184 INSP-Sprinkler Rough-in/Hydro6/18/20036/18/20036/18/2003 12:00:00 AMPPASS
mike; Phone #: ###-#### Sprinkler piping rough in is ok 6/18/2003 3:52:03 PM
FIR03-00317 INSP-Conference6/18/20036/18/20036/18/2003 12:00:00 AMPPASS
Inspection was for supply line cover. The supply line is OK for cover 6/18/2003 3:48:31 PM
BLD03-01064 FIRE-Final Inspection6/18/20036/18/20036/18/2003 12:00:00 AMPFAIL
###-#### Provide "Door to remain unlocked" sticker. Provide verification that the hvac unit is under 2000 cfm. Correct sprinkler deficiancies. Test emergency lights 6/18/2003 3:54:44 PM
FIR03-00110 INSP-Final Inspection6/18/20036/18/20036/18/2003 12:00:00 AMPPASS
Supply line cover, flush and hydro is OK
FIR03-00099 INSP-Final Inspection6/18/20036/18/20036/18/2003 12:00:00 AMPPASS
Supply line cover, flush and hydro is OK
FIR03-00291 INSP-Final Inspection6/18/20036/18/20036/18/2003 12:00:00 AMPFAIL
two drops off of a single 1" outlet in the same area. Needs to be only one drop in same area