ELE04-01663
| Final | 6/18/2004 | 6/18/2004 | 6/18/2004 8:25:03 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 6/18/2004 at 7:45:38 AM. Contact: ###-####. Inspection cancelled from web by: Cathy Chiles
|
ELE04-01806
| Electrical Rough-In | 6/17/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | A | DONE |
|
|
###-#### terry
|
ELE04-01806
| Rough-In Permanent Service | 6/17/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | A | PASS |
|
|
###-#### terry called 300.4, 11/4 for cables
shall not ID 6 or smaller grds or neutrals r/i ok
p/s o/h rec. ok 6/18/2004 8:35:09 AM
|
ELE04-01699
| Rough-In Permanent Service | 6/18/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | A | FAIL |
|
|
see added p/s r/i fail cor. posted called left message 250.148 box in vault, 310.15 (B)(2) derate wires in conduit from p/s to vault 6/18/2004 9:43:43 AM
|
ELE04-01699
| Permanent Service | 6/18/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE03-03402
| Final | 6/17/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | A | FAIL |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no access to inside, outside needs to install bond at p/s, terminate GEC to neutral bus, 314.3 bond bushing in meyers hub, seal all unused openingsin boxes called 6/18/2004 12:27:48 PM
|
ELE04-01807
| Final | 6/17/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | P | PASS |
|
|
Added receptacle for insta-hot in women's restroom.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok 6/18/2004 2:42:46 PM
|
ELE04-01814
| Final | 6/18/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok 6/18/2004 1:29:40 PM
|
ELE04-01409
| Final | 6/18/2004 | 6/18/2004 | 6/18/2004 12:00:00 AM | P | FAIL |
|
|
phil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. posted called 110.3(B) use manufactures listed and approved breakers, bryant sub panel, also seal unused breaker KOs called left message 6/18/2004 2:08:19 PM
|