Inspections for the day of: Friday, June 18, 2004.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00328 INSP-Final Inspection6/15/20046/18/20046/18/2004 12:00:00 AMAFAIL
Connect tamper switches to facp. This work will require permit per review comments. Backflow preventor/vault can be buried. 6/18/2004 9:34:53 AM
FIR04-00021 INSP-Final Inspection6/15/20046/18/20046/18/2004 12:00:00 AMAFAIL
Provide a/v coverage in the corridor per the last correction notice. Change the 30cd strobe to 15cd in Rob's office. Provide signage on doors to facp and sprinkler riser per review note #23. Test low air signal on dry pipe riser 6/18/2004 9:33:41 AM
FIR04-00257 INSP-Final Inspection6/16/20046/18/20046/18/2004 12:00:00 AMAFAIL
Provide clearance per the IMC, between the appliances and the ends of the hood. 6/18/2004 10:23:38 AM
FIR03-00770 INSP-Final Inspection6/17/20046/18/20046/18/2004 12:00:00 AMAPASS
Fire alarm finaled. Alarm contractor is to attach some loose wire to building structural and I'll do a drive by next week to verify. 6/18/2004 1:04:07 PM
FIR04-00349 INSP-Final Inspection6/17/20046/18/20046/18/2004 12:00:00 AMAFAIL
Still need one additional pendant in phase III. See city approved plans for location. 6/18/2004 1:05:26 PM
BLD04-00375 FIRE-Final Inspection6/17/20046/18/20046/18/2004 12:00:00 AMAFAIL
See city approved plans for locations of additional emergency lights and exit signs that need repaired. Provide ADA approved hardware on doors in remodeled areas. Provide one additional sprinkler pendant in phase III. The "E" occupancy doesn't apprear to meet IFC 907.2.3. See review note #2. Provide occupant load signs per review note #12. THIS WAS A LIMITED INSPECTION. CONTRACTOR TO GO OVER REVIEW NOTES AND CALL IN AGAIN 6/18/2004 1:08:50 PM
FIR04-00316 INSP-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPASS
Fire alarm finaled 6/18/2004 1:47:50 PM
FIR04-00362 INSP-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPART
A temporary occupancy was given with Sam and Daves permission for a 90 day period. The fire alarm system needs upgraded. 6/18/2004 3:47:46 PM
FIR03-00448 INSP-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPASS
permit finaled 6/18/2004 3:39:43 PM
BLD04-00489 FIRE-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPASS
Fire life safety finaled
FIR04-00261 INSP-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPASS
Fire sprinklers finaled
FIR03-00554 INSP-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPASS
Permit finaled
BLD03-00602 FIRE-Final Inspection6/18/20046/18/20046/18/2004 12:00:00 AMPPASS
Fire life safety finaled