BLD06-01098
| FIRE-Final Inspection | 6/18/2007 | 6/18/2007 | 6/18/2007 5:28:29 PM | P | PASS |
|
|
life safety passed.
|
FIR07-00503
| INSP-Final Inspection | 6/18/2007 | 6/18/2007 | 6/18/2007 5:26:03 PM | P | PASS |
|
|
permit finaled
|
FIR07-00504
| INSP-Final Inspection | 6/18/2007 | 6/18/2007 | 6/18/2007 5:24:36 PM | P | PASS |
|
|
Permit finaled but not before finding one a/v that did not work and needed replacing and the test redone.
|
BLD06-01099
| FIRE-Final Inspection | 6/18/2007 | 6/18/2007 | 6/18/2007 1:35:17 PM | P | PASS |
|
|
life safety passed
|
BLD06-01096
| FIRE-Final Inspection | 6/18/2007 | 6/18/2007 | 6/18/2007 1:31:22 PM | P | PASS |
|
|
life safety passed
|
FIR05-00536
| INSP-Sprinkler Rough-in | 6/15/2007 | 6/18/2007 | 6/18/2007 12:15:24 PM | A | PASS |
|
|
See the city approved plans for the piping above the hardlids on the 9th floor which is ok to cover.
|
FIR06-00570
| INSP-Final Inspection | 6/13/2007 | 6/18/2007 | 6/18/2007 11:16:18 AM | A | FAIL |
|
|
See the city approved plans for locations where additional a/v's will be required to be installed. These areas were in question on the reviewed plans. Candella needs to be changed on several of the a/v's as marked on the plans. Also the duct smoke detectors are not attached securely to the duct, are oriented the wrong way and have incorrect sample tube lengths. Contractor is to supply the signals as well at the next inspection.
|