FIR09-00070
| FIR-Aging Inspection | 6/18/2009 | 6/18/2009 | 6/18/2009 5:03:52 PM | | DONE |
|
|
Pending site inspection request for work completed.
|
FIR09-00264
| INSP-Sprinkler Rough-in/Hydro | 6/18/2009 | 6/18/2009 | 6/18/2009 5:02:49 PM | P | FAIL |
|
|
Correction list includes blocked upright coverage at the equipment room, missing flexible couplings at the feed main through warehouse wall, provide listed air maintenance device, noted dry valve installed does not match type submitted, remote test connection has been relocated from where shown on approved plans.
|
FIR09-00156
| INSP-Final Inspection | 6/18/2009 | 6/18/2009 | 6/18/2009 4:58:20 PM | P | PASS |
|
|
Corrections verified for completion, final inspection passed, fire alarm permit finaled.
|
BLD09-00228
| FIRE-Final Inspection | 6/17/2009 | 6/18/2009 | 6/18/2009 4:56:28 PM | A | PASS |
|
|
Final fire life safety inspection completed satisfactory.
|
FIR08-00439
| INSP-Sprinkler Rough-in/Hydro | 6/17/2009 | 6/18/2009 | 6/18/2009 4:55:12 PM | A | FAIL |
|
|
Noted one obstructed head at the master closet by an adjacent surface mounted light fixture, tape and paper at two pendents removed while on site, remainder of work is acceptable.
|
FIR09-00363
| INSP-Sprinkler Rough-in | 6/17/2009 | 6/18/2009 | 6/18/2009 4:52:09 PM | A | PART |
|
|
System 12 office area overhead installation is approved for cover as noted on plans with the exception of two heads to be relocated due to blockage/overspaced coverage.
|