Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00070 FIR-Aging Inspection6/18/20096/18/20096/18/2009 5:03:52 PM DONE
Pending site inspection request for work completed.
FIR09-00264 INSP-Sprinkler Rough-in/Hydro6/18/20096/18/20096/18/2009 5:02:49 PMPFAIL
Correction list includes blocked upright coverage at the equipment room, missing flexible couplings at the feed main through warehouse wall, provide listed air maintenance device, noted dry valve installed does not match type submitted, remote test connection has been relocated from where shown on approved plans.
FIR09-00156 INSP-Final Inspection6/18/20096/18/20096/18/2009 4:58:20 PMPPASS
Corrections verified for completion, final inspection passed, fire alarm permit finaled.
BLD09-00228 FIRE-Final Inspection6/17/20096/18/20096/18/2009 4:56:28 PMAPASS
Final fire life safety inspection completed satisfactory.
FIR08-00439 INSP-Sprinkler Rough-in/Hydro6/17/20096/18/20096/18/2009 4:55:12 PMAFAIL
Noted one obstructed head at the master closet by an adjacent surface mounted light fixture, tape and paper at two pendents removed while on site, remainder of work is acceptable.
FIR09-00363 INSP-Sprinkler Rough-in6/17/20096/18/20096/18/2009 4:52:09 PMAPART
System 12 office area overhead installation is approved for cover as noted on plans with the exception of two heads to be relocated due to blockage/overspaced coverage.