ELE10-00381
| Electrical Rough-In | 6/18/2010 | 6/18/2010 | 6/18/2010 3:42:15 PM | P | CANC |
|
|
Inspection requested from web by: Jim Williams Phone #: ###-#### called, wrong address and job called in, fee due
|
ELE10-01313
| Rough-In Permanent Service | 6/18/2010 | 6/18/2010 | 6/18/2010 2:59:16 PM | P | PASS |
|
|
ready for inspection Inspection requested from web by: gary batten Phone #: ###-#### ric ok, p/s u/g n ok
|
ELE10-01312
| Permanent Service | 6/18/2010 | 6/18/2010 | 6/18/2010 2:25:06 PM | P | PASS |
|
|
ready for inspection Inspection requested from web by: gary batten Phone #: ###-#### p/s u/g n ok
|
ELE10-01134
| Electrical Rough-In | 6/18/2010 | 6/18/2010 | 6/18/2010 1:43:25 PM | P | FAIL |
|
|
Colt Phone #: ###-#### called, bad number, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 210.52 shall install receptacle within 6' of doors (rear), 312.5 all conductors entering enclosure shall have abrasion protection, 334.23 shall protect cables within 6' of attic access, 250.86 shall ground metal boxes, 334.30 shall secure nm cable within 12" of termination at panel,110.3(B) listed equipment shall be installed per instructions (clamps at panel),BCC shall wire all boxes and provide make-up, NOTE: corrections shall be made within 5 working days or further action will be taken
|
ELE10-01357
| Electrical Rough-In | 6/18/2010 | 6/18/2010 | 6/18/2010 12:26:44 PM | P | PASS |
|
|
Dave ###-#### ric ok
|
ELE10-01349
| Final | 6/17/2010 | 6/18/2010 | 6/18/2010 11:40:23 AM | A | PASS |
|
|
Inspection requested from web by: Therrin Robertson Phone #: ###-#### ok to final
|
ELE10-00945
| Final | 6/17/2010 | 6/18/2010 | 6/18/2010 10:51:03 AM | A | PASS |
|
|
Mike Phone #: ###-#### ok to final
|
ELE10-01286
| Electrical Rough-In | 6/17/2010 | 6/18/2010 | 6/18/2010 10:35:35 AM | A | PASS |
|
|
steve Phone #: ###-#### corrections made, ric ok
|
ELE10-01345
| Electrical Rough-In | 6/17/2010 | 6/18/2010 | 6/18/2010 9:52:18 AM | A | PASS |
|
|
misc electrical rough in any questions call Rob @ ###-#### Inspection requested from web by: Andy Rose Phone #: ###-#### ric ok
|
ELE10-01203
| Electrical Rough-In | 6/18/2010 | 6/18/2010 | 6/18/2010 9:23:43 AM | A | PASS |
|
|
Call Mr Steven Harris for inspection on 2nd floor of AGC building. Inspection requested from web by: Loren Ramsey Phone #: ###-#### ok to cover ceiling only
|
ELE10-01336
| Electrical Rough-In | 6/17/2010 | 6/18/2010 | 6/18/2010 8:40:51 AM | A | PASS |
|
|
cover inspection for lobby. Inspection requested from web by: Tyler Bowen Phone #: ###-#### met contractor, ok to cover lobby only
|
ELE10-01066
| Final | 6/17/2010 | 6/18/2010 | 6/18/2010 8:09:32 AM | A | PASS |
|
|
Inspection requested from web by: Zane Robertson Phone #: ###-#### ok to final
|
ELE10-00372
| Final | 6/18/2010 | 6/18/2010 | 6/18/2010 6:41:13 AM | A | PASS |
|
|
ok to final
|
ELE09-02130
| Final | 6/18/2010 | 6/18/2010 | 6/18/2010 6:38:46 AM | A | PASS |
|
|
ok to final
|
ELE09-02312
| Final | 6/18/2010 | 6/18/2010 | 6/18/2010 6:36:01 AM | A | PASS |
|
|
ok to final
|
ELE09-02094
| Final | 6/18/2010 | 6/18/2010 | 6/18/2010 6:34:19 AM | A | PASS |
|
|
ok to final
|
ELE08-00377
| ELE-Aging Inspection | 6/18/2010 | 6/18/2010 | 6/18/2010 6:31:06 AM | | DONE |
|
|
see doc expire
|
ELE08-00377
| DOC - Permit Expired | 6/18/2010 | 6/18/2010 | 6/18/2010 6:30:53 AM | A | PASS |
|
|
no activity
|
ELE08-00943
| ELE-Aging Inspection | 6/18/2010 | 6/18/2010 | 6/18/2010 6:29:28 AM | | DONE |
|
|
see doc expire
|
ELE08-00943
| DOC - Permit Expired | 6/18/2010 | 6/18/2010 | 6/18/2010 6:29:13 AM | A | PASS |
|
|
no activity
|