BLD12-01454
| FIRE-Final Inspection | 6/15/2012 | 6/18/2012 | 6/18/2012 3:34:21 PM | P | FAIL |
|
|
Remove or repair the exit sign/emergency light. Mount the fire extinguishers and provide covers for the electrical outlets.
|
BLD10-02771
| FIRE-Conference | 6/18/2012 | 6/18/2012 | 6/18/2012 3:11:32 PM | P | DONE |
|
|
Jeremy wanted a conference/walk through. I found one upright sprinkler head in a second floor room that is blocked by a surface mounted light. Also several pendant heads in the truck bay have ordinary temp heads in locations where intermediate and high temp. heads are required at the unit heaters. We also went over general life safety requirements.
|
FIR11-00483
| INSP-Final Inspection | 6/18/2012 | 6/18/2012 | 6/18/2012 3:10:12 PM | P | CANC |
|
|
Jeremy actually wanted a conference/walk through. I found one upright sprinkler head in a second floor room that is blocked by a surface mounted light. Also several pendant heads in the truck bay have ordinary temp heads in locations where intermediate and high temp. heads are required at the unit heaters.
|
FIR12-00021
| INSP-Sprinkler Rough-in | 6/15/2012 | 6/18/2012 | 6/18/2012 11:52:49 AM | A | PASS |
|
|
The remaining underground supply piping is ok to cover.
|
FIR11-00543
| INSP-Sprinkler Rough-in/Hydro | 6/15/2012 | 6/18/2012 | 6/18/2012 10:05:33 AM | A | FAIL |
|
|
Underground Hydro inspection for the chiller room failed due to visable drop in pressure on the guage.
|