Inspections for the day of: Monday, June 18, 2012.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01454 FIRE-Final Inspection6/15/20126/18/20126/18/2012 3:34:21 PMPFAIL
Remove or repair the exit sign/emergency light. Mount the fire extinguishers and provide covers for the electrical outlets.
BLD10-02771 FIRE-Conference6/18/20126/18/20126/18/2012 3:11:32 PMPDONE
Jeremy wanted a conference/walk through. I found one upright sprinkler head in a second floor room that is blocked by a surface mounted light. Also several pendant heads in the truck bay have ordinary temp heads in locations where intermediate and high temp. heads are required at the unit heaters. We also went over general life safety requirements.
FIR11-00483 INSP-Final Inspection6/18/20126/18/20126/18/2012 3:10:12 PMPCANC
Jeremy actually wanted a conference/walk through. I found one upright sprinkler head in a second floor room that is blocked by a surface mounted light. Also several pendant heads in the truck bay have ordinary temp heads in locations where intermediate and high temp. heads are required at the unit heaters.
FIR12-00021 INSP-Sprinkler Rough-in6/15/20126/18/20126/18/2012 11:52:49 AMAPASS
The remaining underground supply piping is ok to cover.
FIR11-00543 INSP-Sprinkler Rough-in/Hydro6/15/20126/18/20126/18/2012 10:05:33 AMAFAIL
Underground Hydro inspection for the chiller room failed due to visable drop in pressure on the guage.