Inspections for the day of: Wednesday, June 18, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01537 Final6/18/20146/18/20146/18/2014 3:58:03 PMPPASS
Contact: Justin Hugo Phone #: ###-#### >> Inspection requested via web by Deb Gooden Final ok
ELE12-02735 Conference6/18/20146/18/20146/18/2014 3:56:34 PMPDONE
We are requesting an electrical consult for today June 18th in the aftermoon. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Discussed direct burial depth under ambulance cover, due to vehicle access 24" minimum cover required but due to solid concrete bases note 5 to 300.5 states shallower depth acceptable if encased in min of 2" concrete.
ELE13-03546 Electrical Rough-In6/18/20146/18/20146/18/2014 1:26:46 PMPPASS
2fl walls - MIke Phone #: ###-#### 2nd floor walls and hard lid rough in ok cover
ELE14-01556 Electrical Rough-In6/17/20146/18/20146/18/2014 12:46:46 PMPPASS
Additional bonding & underground (contractor added (6) pool lights) Phone #: ###-#### >> Inspection requested via web by Lars Johnson Bonding rough in ok cover
ELE13-01288 Final6/13/20146/18/20146/18/2014 12:28:12 PMPPASS
Dan Phone #: ###-#### Final ok
ELE13-02187 Final6/17/20146/18/20146/18/2014 11:30:52 AMAPASS
lights in front porch area Phone #: ###-#### >> Inspection requested via web by PAT MILLER Final ok
ELE14-00373 Final6/18/20146/18/20146/18/2014 11:10:01 AMAPASS
Call Dylan ###-#### for access. Half hour ahead will be great. Thank you Phone #: ###-#### >> Inspection requested via web by daniel bibikov Final ok
ELE14-01555 Rough-In Permanent Service6/17/20146/18/20146/18/2014 10:40:30 AMANR
Phone #: ###-#### >> Inspection requested via web by mike brown Make up, nail plates. Will reschedule
ELE13-03048 Final6/17/20146/18/20146/18/2014 10:21:32 AMAPASS
0505enter Phone #: ###-#### >> Inspection requested via web by Dan Rohl Final ok
ELE14-01064 Final6/16/20146/18/20146/18/2014 9:51:41 AMACANC
Phone #: ###-#### Called asked to cancel and they will reschedule
ELE13-03575 Final6/17/20146/18/20146/18/2014 9:50:49 AMAFAIL
lock box code is 7534 Phone #: ###-#### >> Inspection requested via web by shane miller 210.8- All 120 volt receptical outlets installed with in 6' of sinks shall have GFCI protection. All receptical outlets serving kitchen counter tops shall have GFCI protection.
210.63- Closet luminaire shall have totally enclosed lamp.
210.52(D)- A receptical outlet shall be located adjacent to each bathroom basin.
406.11- All 120 volt receptical outlets shall be tamper resistant type
ELE14-01591 Final6/17/20146/18/20146/18/2014 9:01:19 AMACANC
Phone #: ###-#### >> Inspection requested via web by HZ ZAHIC Needed rough in permenant service
ELE14-01591 Rough-In Permanent Service6/18/20146/18/20146/18/2014 9:01:01 AMPPASS
Phone #: ###-#### >> Inspection requested via web by HZ ZAHIC Rough in ok cover p/s u/g n ok