FIR15-00349
| INSP-Supply line flush | 6/18/2015 | 6/18/2015 | 6/18/2015 1:32:39 PM | P | PASS |
|
|
Underground supply line flush passed
|
FIR15-00351
| INSP-Supply line flush | 6/18/2015 | 6/18/2015 | 6/18/2015 12:08:43 PM | P | PASS |
|
|
Underground supply line flush passed.
|
FIR15-00360
| INSP-Supply line flush | 6/17/2015 | 6/18/2015 | 6/18/2015 10:24:25 AM | A | CANC |
|
|
Wrong permit scheduled
|
FIR15-00359
| INSP-Supply line flush | 6/17/2015 | 6/18/2015 | 6/18/2015 10:22:55 AM | A | CANC |
|
|
wrong permit scheduled
|
FIR12-00260
| INSP-Alarm Testing | 6/17/2015 | 6/18/2015 | 6/18/2015 9:36:50 AM | A | FAIL |
|
|
Todays inspection was for the new addition. Smoke detectors did not alarm at the panel, Panel did not receive trouble signal from new addition. Smoke detectors to be mounted atleast 3'-0" from ceiling fans. I stopped testing until issues have been resolved.
|
FIR14-00768
| INSP-Sprinkler Rough-in | 6/17/2015 | 6/18/2015 | 6/18/2015 8:27:24 AM | A | PASS |
|
|
Tenting and rough-in inspection passed. Piping can be covered.
|