Inspections for the day of: Tuesday, June 19, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02064 Electrical Rough-In6/19/20076/19/20076/19/2007 3:43:37 PMPCANC
jared - underground; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called u/g for phone service conduit we do not inspect that, only the inside blding conduit
ELE07-02200 Temporary Service6/19/20076/19/20076/19/2007 3:33:27 PMPFAIL
greg ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
fee due corr. called 312.5 needs conn for GEC, 110.12(C) clean dirt from t/s and receptacles, 250.52(A)(5)7250.23(G) short grd rod
ELE07-02202 Temporary Service6/18/20076/19/20076/19/2007 3:06:48 PMAPASS
WAYNE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles survey called 110.3(B) use only sq D breakers t/s u/g new ok
ELE07-00769 Electrical Rough-In6/19/20076/19/20076/19/2007 2:48:27 PMPPART
up&down walls and hard ceilings ok needs sign circuit 600.5
ELE07-00768 Electrical Rough-In6/19/20076/19/20076/19/2007 2:47:43 PMPPART
r/i up&down stairs walls and fard ceilings ok needs required sign branch circuit 600.5
ELE07-01431 Electrical Rough-In6/19/20076/19/20076/19/2007 2:17:53 PMPCANC
Scheduled by a contractor via Hello! on 6/19/2007 at 10:54:35 AM. Contact: ###-####.
ELE07-01429 Electrical Rough-In6/19/20076/19/20076/19/2007 2:17:40 PMPCANC
Scheduled by a contractor via Hello! on 6/19/2007 at 10:53:36 AM. Contact: ###-####.
ELE07-01253 Final6/15/20076/19/20076/19/2007 1:47:10 PMPPASS
Scheduled by a contractor via Hello! on 6/15/2007 at 2:31:00 PM. ok card signed
ELE07-01617 Rough-In Permanent Service6/19/20076/19/20076/19/2007 1:24:12 PMPPASS
gene Phone #: ###-#### r/i p/s u/g N ok
ELE07-01252 Final6/15/20076/19/20076/19/2007 12:36:36 PMAPASS
Scheduled by a contractor via Hello! on 6/15/2007 at 2:29:41 PM. ok card signed
ELE07-01327 Final6/19/20076/19/20076/19/2007 11:19:16 AMAPASS
###-#### Internet Inspection Request from: Todd Holbrook ok no card
ELE07-01722 Electrical Rough-In6/18/20076/19/20076/19/2007 10:41:17 AMAPART
MITCH PAGE - HE WILL MEET @ JOB SITE. UFER GROUND TO BE INSPECTED Phone #: ###-#### Internet Inspection Request from: Randy Vail ok
ELE07-01617 Rough-In Permanent Service6/19/20076/19/20076/19/2007 10:17:52 AMPCANC
Gene ###-####. Jack - This is the one that I needed that the permits were switched to correct the address problem out there. Pleae let me know if there is any questions. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE07-02065 Final6/18/20076/19/20076/19/2007 10:14:56 AMAPASS
randy ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok card signed
ELE07-02024 Final6/18/20076/19/20076/19/2007 9:47:33 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier called survey needs recept within 25ft of new a/c 210.63
ELE07-02083 Electrical Rough-In6/19/20076/19/20076/19/2007 9:11:37 AMAFAIL
Scheduled by a contractor via Hello! on 6/19/2007 at 6:55:17 AM. Contact: ###-####. corr. called l 300.4 nail plates and 11/4", 210.52(A&B) needs outlet kit west wall, 334.23 protect cables by attic accesses
ELE07-02043 Electrical Rough-In6/18/20076/19/20076/19/2007 8:16:50 AMAPART
steve - partial trench; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang u/g ok
ELE07-01616 Rough-In Permanent Service6/18/20076/19/20076/19/2007 12:00:00 AMACANC
Gene ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson double inspection - cancelled per shelly 6/19/2007