Inspections for the day of: Tuesday, June 19, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01705 Final6/19/20076/19/20076/19/2007 4:03:41 PMPPASS
vern - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to final
ELE07-01114 Final6/19/20076/19/20076/19/2007 3:45:48 PMPPASS
jamie - re-inspection Phone #: ###-#### ok to final, corr made
ELE07-02213 Electrical Rough-In6/19/20076/19/20076/19/2007 3:27:25 PMPNR
steve Phone #: ###-#### called contr, told to be sure equipotential plane ready, use min 6 gage mesh, put blocks under, u/g will be ok
ELE07-02002 Rough-In Permanent Service6/19/20076/19/20076/19/2007 2:48:56 PMPPASS
eric ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, called contr, p/s u/g n ok
ELE07-01144 Electrical Rough-In6/19/20076/19/20076/19/2007 1:50:22 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton soffits only ok to cover
ELE07-02192 Temporary Service6/18/20076/19/20076/19/2007 1:19:34 PMAFAIL
CONTACT: STEVE HESS Phone #: ###-#### Internet Inspection Request from: Deb Gooden called, left corr notice, nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 250.53 (G) rod shall not be over 45 degree, 250.24(A) gec shall tie to each service to the grounded srevice conductor, 314.28(A)(2) pull box shall be sized per number of raceways entering and leaving for angle pulls(22" min?), 110.14(A) connections shall be tight
ELE07-02211 Electrical Rough-In6/19/20076/19/20076/19/2007 12:47:04 PMPPART
Shane Vanleuven ###-#### Thank-You Phone #: ###-#### Internet Inspection Request from: Debby Ellis ric basement except mech room ok
ELE07-00920 Final6/18/20076/19/20076/19/2007 11:59:43 AMAPASS
call to find out how to gain access Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final
ELE07-00918 Final6/18/20076/19/20076/19/2007 11:30:23 AMAPASS
call to find out how to gain access Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final
ELE07-02186 Final6/19/20076/19/20076/19/2007 10:58:35 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Todd Sellman ok to final
ELE07-02194 Final6/19/20076/19/20076/19/2007 10:39:34 AMAFAIL
Scheduled by a contractor via Hello! on 6/19/2007 at 7:29:32 AM. called left corr notice, nec 110.3(B) listed equipment shall be installed per instructions, 110.14(A) connections shall be tight, 110.12(C) paint shall not contaminate wiring, 250.52(A) shall use metal water pipe for grounding electrode, 250.64(C) grounding electrode conductor shall be installed in one continuous length without a splice or joint
ELE07-00836 Conference6/18/20076/19/20076/19/2007 10:00:04 AMADONE
roger; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang talked about new shop and service, u'g, wiring shop
ELE07-00147 Final6/18/20076/19/20076/19/2007 9:38:39 AMAPASS
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang items that weren't ready done , ok to final, signed occupancy card
ELE07-01650 Final6/19/20076/19/20076/19/2007 8:50:27 AMAPART
Scheduled by a contractor via Hello! on 6/19/2007 at 6:55:01 AM. Contact: ###-####. looked at x-ray and ok, called contr to do panel schedule and be sure occ card there, then call for final
ELE07-02100 Electrical Rough-In6/19/20076/19/20076/19/2007 8:49:18 AMPCANC
neil ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Patricia Smith
ELE07-02187 Electrical Rough-In6/18/20076/19/20076/19/2007 8:29:40 AMAPASS
inspection on new conduits installed for cash wrap. any questions call Tate @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to cover u/g, walls and clg
ELE07-00886 Final6/18/20076/19/20076/19/2007 8:07:04 AMAFAIL
Phase 2 Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton talked with contr, correction notice not done for breakers
ELE07-02186 Permanent Service6/18/20076/19/20076/18/2007 4:24:48 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Todd Sellman p/s o/h rec ok