ELE07-01705
| Final | 6/19/2007 | 6/19/2007 | 6/19/2007 4:03:41 PM | P | PASS |
|
|
vern - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to final
|
ELE07-01114
| Final | 6/19/2007 | 6/19/2007 | 6/19/2007 3:45:48 PM | P | PASS |
|
|
jamie - re-inspection Phone #: ###-#### ok to final, corr made
|
ELE07-02213
| Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 3:27:25 PM | P | NR |
|
|
steve Phone #: ###-#### called contr, told to be sure equipotential plane ready, use min 6 gage mesh, put blocks under, u/g will be ok
|
ELE07-02002
| Rough-In Permanent Service | 6/19/2007 | 6/19/2007 | 6/19/2007 2:48:56 PM | P | PASS |
|
|
eric ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, called contr, p/s u/g n ok
|
ELE07-01144
| Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 1:50:22 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton soffits only ok to cover
|
ELE07-02192
| Temporary Service | 6/18/2007 | 6/19/2007 | 6/19/2007 1:19:34 PM | A | FAIL |
|
|
CONTACT: STEVE HESS Phone #: ###-#### Internet Inspection Request from: Deb Gooden called, left corr notice, nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 250.53 (G) rod shall not be over 45 degree, 250.24(A) gec shall tie to each service to the grounded srevice conductor, 314.28(A)(2) pull box shall be sized per number of raceways entering and leaving for angle pulls(22" min?), 110.14(A) connections shall be tight
|
ELE07-02211
| Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 12:47:04 PM | P | PART |
|
|
Shane Vanleuven ###-#### Thank-You Phone #: ###-#### Internet Inspection Request from: Debby Ellis ric basement except mech room ok
|
ELE07-00920
| Final | 6/18/2007 | 6/19/2007 | 6/19/2007 11:59:43 AM | A | PASS |
|
|
call to find out how to gain access Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final
|
ELE07-00918
| Final | 6/18/2007 | 6/19/2007 | 6/19/2007 11:30:23 AM | A | PASS |
|
|
call to find out how to gain access Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final
|
ELE07-02186
| Final | 6/19/2007 | 6/19/2007 | 6/19/2007 10:58:35 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Sellman ok to final
|
ELE07-02194
| Final | 6/19/2007 | 6/19/2007 | 6/19/2007 10:39:34 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/19/2007 at 7:29:32 AM. called left corr notice, nec 110.3(B) listed equipment shall be installed per instructions, 110.14(A) connections shall be tight, 110.12(C) paint shall not contaminate wiring, 250.52(A) shall use metal water pipe for grounding electrode, 250.64(C) grounding electrode conductor shall be installed in one continuous length without a splice or joint
|
ELE07-00836
| Conference | 6/18/2007 | 6/19/2007 | 6/19/2007 10:00:04 AM | A | DONE |
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang talked about new shop and service, u'g, wiring shop
|
ELE07-00147
| Final | 6/18/2007 | 6/19/2007 | 6/19/2007 9:38:39 AM | A | PASS |
|
|
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang items that weren't ready done , ok to final, signed occupancy card
|
ELE07-01650
| Final | 6/19/2007 | 6/19/2007 | 6/19/2007 8:50:27 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 6/19/2007 at 6:55:01 AM. Contact: ###-####. looked at x-ray and ok, called contr to do panel schedule and be sure occ card there, then call for final
|
ELE07-02100
| Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 8:49:18 AM | P | CANC |
|
|
neil ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Patricia Smith
|
ELE07-02187
| Electrical Rough-In | 6/18/2007 | 6/19/2007 | 6/19/2007 8:29:40 AM | A | PASS |
|
|
inspection on new conduits installed for cash wrap. any questions call Tate @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to cover u/g, walls and clg
|
ELE07-00886
| Final | 6/18/2007 | 6/19/2007 | 6/19/2007 8:07:04 AM | A | FAIL |
|
|
Phase 2 Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton talked with contr, correction notice not done for breakers
|
ELE07-02186
| Permanent Service | 6/18/2007 | 6/19/2007 | 6/18/2007 4:24:48 PM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Sellman p/s o/h rec ok
|