Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00727 INSP-Sprinkler Rough-in/Hydro6/19/20076/19/20076/20/2007 2:46:38 PMPPART
OH rough-in is acceptable for the 1st and 2nd floor wet systems, noted field mods on the 1st floor, 2nd floor dead end 1" pipe in the wall to be removed and capped above the ceiling.
BLD06-03094 FIRE-Final Inspection6/19/20076/19/20076/19/2007 3:25:10 PMPPART
Need final for the project related fire sprinkler permit, noted tape at two sprinkler heads in the mezz. storage area to be removed, post one additional PFE at the front entrance as discussed, remainder of fire life safety items appear acceptable.
FIR07-00485 INSP-Sprinkler Rough-in/Hydro6/19/20076/19/20076/19/2007 2:36:15 PMPPART
Approved dry system modifications for cover, noted four plugged tees which will need reconfigured to avoid water collection and freeze potential.
FIR07-00078 INSP-Final Inspection6/18/20076/19/20076/19/2007 1:49:01 PMPPART
UG supply flush completed okay, final pending balance of permit work to be finished.
BLD07-00317 FIRE-Final Inspection6/19/20076/19/20076/19/2007 12:45:21 PMPPASS
One emergency light repaired while on site, the provided PFE attatched as agreed, fire life safety inspection passed.
FIR06-00728 INSP-Sprinkler Rough-in6/18/20076/19/20076/19/2007 12:38:33 PMAFAIL
Wrong permit number called in for inspection, was intended for a project related tenant improvement under FIR07-00270. Inspection failed due to overspaced heads at five locations, two heads in a conference room are cut in a the wrong ceiling height, missing approved plans which are required to be on site as a condition of the permit, a hold currently exists on this permit due to overdue fees.
BLD07-01071 FIRE-Final Inspection6/19/20076/19/20076/19/2007 12:32:00 PMPPASS
Required corrections verified, fire life safety passed.
FIR07-00422 INSP-Final Inspection6/19/20076/19/20076/19/2007 12:29:40 PMPPASS
Fire sprinkler permit finaled.
FIR07-00030 FIR-Aging Inspection6/19/20076/19/20076/19/2007 11:41:13 AM DONE
Under construction, work in progress.
FIR07-00537 INSP-Final Inspection6/18/20076/19/20076/19/2007 10:55:35 AMAPASS
Fire alarm modifications passed inspection, permit finaled.
MIS07-00135 FIR-Final6/18/20076/19/20076/19/2007 10:18:42 AMAPASS
Corrections completed, fire life safety inspection passed.