Inspections for the day of: Thursday, June 19, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01481 Final6/19/20086/19/20086/19/2008 3:59:54 PMPPASS
Scheduled by a contractor via Hello! on 6/19/2008 at 9:40:32 AM. Contact: ###-####.
no esc in project
ELE08-01645 Permanent Service6/19/20086/19/20086/19/2008 3:10:59 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Andy Derrick
P/S O/H R Ok
ELE08-00658 Rough-In Permanent Service6/19/20086/19/20086/19/2008 2:55:21 PMPFAIL
james Phone #: ###-####
6 in free conductor at all boxes no permit no violations to be retained and proper connectors required on romex
ELE08-00658 Permanent Service6/18/20086/19/20086/19/2008 2:34:12 PMPPASS
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
P/S O/H R Ok
ELE08-01652 Rough-In Permanent Service6/19/20086/19/20086/19/2008 1:30:18 PMPPASS
Wired a new Qwest power pedestal and phone cabinet. Tech is Brian @ ###-#### if you have questions. Thanks, Dan. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
no esc in project
P/S U/G N Ok
ELE08-01652 DOC - Permit Finaled6/19/20086/19/20086/19/2008 1:29:02 PMPPASS
ELE08-00838 Final6/18/20086/19/20086/19/2008 11:33:06 AMAPASS
The pole light is stood but the City of Boise will finish the job when they get a head for the pole light. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
ELE08-01646 Electrical Rough-In6/18/20086/19/20086/19/2008 10:35:05 AMAPASS
Check existing service for safty so that Idaho Power can hook up to it for temp purposes to feed two GFCI durring clean up before we put the new service in. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
ELE08-01646 Temporary Service6/19/20086/19/20086/19/2008 10:34:55 AMPPASS
Check existing service for safty so that Idaho Power can hook up to it for temp purposes to feed two GFCI durring clean up before we put the new service in. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
ok for T/S O/H R Ok
ELE08-01499 Permanent Service6/18/20086/19/20086/19/2008 10:21:34 AMAFAIL
SCOTT Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
replace metal connector with plastic on GEC and drive ground rods flush
ELE08-01631 Electrical Rough-In6/18/20086/19/20086/19/2008 10:01:17 AMAPART
ELECTRICAL ROUGH IN FOR THE WALLS AND CIELING Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
upstairs ok not under 517 per Jim.
ELE08-00507 Final6/18/20086/19/20086/19/2008 9:30:34 AMAPASS
Larry Phone #: ###-####
no esc permit
ELE08-01588 Final6/18/20086/19/20086/19/2008 9:13:43 AMAPASS
This is for a final on this job. Thank you very much and Mark Hood will be the contact person. Have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
final with survey for required lighting and recep outlets.
ELE08-01644 Rough-In Permanent Service6/18/20086/19/20086/19/2008 8:26:49 AMACANC
This Qwest cabinet is almost in the driveway of the house at 2515 N. Lander. Tech is Brian @ ###-#### if you have questions. Qwest Job # 8231aqy. Thanks Dan. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
confusion over address