Inspections for the day of: Thursday, June 19, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00674 ELE-Aging Inspection6/19/20086/19/20086/23/2008 8:04:39 AM DONE
see final
ELE06-04665 Final6/13/20086/19/20086/19/2008 3:53:20 PMPFAIL
Boun Phone #: ###-#### met owner, told to provide 18"x24" access hatch for tub per mfgr's instruction, label panels, provide abrasion protection for gec at meter, u/g ok for grounding electrode, rest ok
ESC06-01396 General Inspection6/19/20086/19/20086/19/2008 3:29:18 PMPPASS
looked ok
ESC06-01062 General Inspection6/19/20086/19/20086/19/2008 3:25:12 PMPPASS
looked ok
ESC08-00323 General Inspection6/19/20086/19/20086/19/2008 3:23:49 PMAPASS
looked ok
ESC08-00415 General Inspection6/19/20086/19/20086/19/2008 3:22:53 PMACANC
sign up, looked ok
ELE07-03967 Final6/19/20086/19/20086/19/2008 2:33:22 PMPPASS
Contact is Toby Groves ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis corrections made, ok to final, signed occupancy card, no esc this project
ELE08-01643 Permanent Service6/18/20086/19/20086/19/2008 2:15:20 PMPPASS
nick - after 2:00 if possible please Phone #: ###-#### p/s o/h rec ok, no esc
ELE08-01552 Final6/18/20086/19/20086/19/2008 12:41:11 PMPFAIL
Cieling inspection for cover. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called contractor, BCC no violations shall be retained, approved set of plans shall be on job,NEC 725.3(B) abandoned class 2,3, and pltc cables shall be removed, 358.30(A) emt shall be secured within 3' of box, 330.30(B) mc shall be secured within 12" of box, 110.12(A) unused openings shall be closed, 250.8 metal enclosures shall be grounded, 362.30(A) ent shall be secured within 3' of box
ELE06-04542 Final6/19/20086/19/20086/19/2008 10:06:23 AMAPASS
ok to final, unit removed, no esc
ELE08-00949 Final6/18/20086/19/20086/19/2008 9:47:29 AMAPASS
Terry Phone #: ###-#### ok to final, signed structural card
ELE08-01622 Final6/18/20086/19/20086/19/2008 9:45:15 AMAPASS
Terry Phone #: ###-#### ok to final, signed occupancy card, no esc
ELE08-01065 Final6/18/20086/19/20086/19/2008 9:10:37 AMAPASS
Whistler Point Apartments Clubhouse. Contact is Brian Cornell.
Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok to final, signed structural card
ELE08-01567 Electrical Rough-In6/18/20086/19/20086/19/2008 8:48:34 AMAFAIL
main underground Phone #: ###-#### Internet Inspection Request from: Lynn Cable called, left correction notice, nec 352.26 there shall not be over 360 degrees total bends in rnc between pull points
ELE08-00984 Final6/18/20086/19/20086/19/2008 8:22:23 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Adam Staigle ok to final, no esc
ELE08-00283 Final6/18/20086/19/20086/19/2008 7:56:58 AMAPART
Robert Phone #: ###-#### called contractor to reschedule for tuesday to do all 6 permits in order to find power sources fo machines, no esc