FIR07-00971
| INSP-Final Inspection | 6/18/2009 | 6/19/2009 | 6/22/2009 5:11:38 PM | P | PART |
|
|
See inspection comments 6/22.
|
BLD09-00968
| FIRE-Final Inspection | 6/19/2009 | 6/19/2009 | 6/19/2009 4:42:11 PM | P | PASS |
|
|
Life safety inspection passed with the exception of the manual thumbturn at the main entry exit door to be removed prior to structural final. Fire extinguisher locations okayed while on site.
|
FIR09-00248
| INSP-Sprinkler Rough-in/Hydro | 6/18/2009 | 6/19/2009 | 6/19/2009 3:46:20 PM | P | PART |
|
|
Unit 514 Building J okayed for cover, noted missing SW head at the understair closet.
|
FIR09-00353
| INSP-Final Inspection | 6/18/2009 | 6/19/2009 | 6/19/2009 2:25:10 PM | A | PASS |
|
|
On site fire alarm testing passed, permit approved for final.
|
FIR07-01032
| INSP-Sprinkler Rough-in | 6/18/2009 | 6/19/2009 | 6/19/2009 1:59:51 PM | P | DEFR |
|
|
jim Phone #: ###-####
|
BLD08-01953
| FIRE-Final Inspection | 6/18/2009 | 6/19/2009 | 6/19/2009 12:35:22 PM | A | PASS |
|
|
Life safety inspection completed acceptable, no inspection record on site for signature.
|
FIR09-00264
| INSP-Sprinkler Rough-in/Hydro | 6/18/2009 | 6/19/2009 | 6/19/2009 12:32:34 PM | A | PART |
|
|
Overhead hydrostatic testing for the new dry system passed, also reinspected C/N items from previous visit.
|
BLD08-01651
| FIRE-Final Inspection | 6/18/2009 | 6/19/2009 | 6/19/2009 11:23:44 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable.
|
FIR09-00079
| FIR-Aging Inspection | 6/19/2009 | 6/19/2009 | 6/19/2009 11:07:26 AM | | DONE |
|
|
Pending site inspection request for work completed.
|
BLD08-02513
| FIRE-Final Inspection | 6/18/2009 | 6/19/2009 | 6/19/2009 11:06:27 AM | A | PASS |
|
|
Corrections field verified, life safety inspection passed. NOTE: signature card not available.
|