FIR11-00662
| INSP-Alarm Testing | 6/19/2012 | 6/19/2012 | 6/19/2012 3:55:21 PM | P | PASS |
|
|
East wing tamper valve for Shilo Sprinkler passed functional testing.
|
BLD12-01430
| FIRE-Final Inspection | 6/18/2012 | 6/19/2012 | 6/19/2012 3:20:51 PM | P | PASS |
|
|
life safety passed
|
FIR12-00161
| INSP-Final Inspection | 6/19/2012 | 6/19/2012 | 6/19/2012 3:20:12 PM | P | FAIL |
|
|
Todays inspection was for a building walk through. I found pendant heads blocked by lights in the third floor library. Pendant head bent in room 317. Pendants covered in rooms 328 and 316 and in the corridor closet outside of room 314. Three pendant heads are also covered in the area "A" south third floor corridor. The sidewall heads in the fourth floor exterior common balcony are located with the deflectors at 2 1/2" to 3" below the ceiling. Need verification they are listed for this. The first and second floors east of the fire wall has not been inspected yet since the light fixtures have not been installed yet. I did note that some of the corridor pendants in the two room apartments are located close to electrical boxes so if lights are installed obstruction may be present. Also washer and dryers are being installed in many of the closets in the residence rooms. The sprinkler pendants in these rooms are 155 degree which may not be high enough temperature. Tom, the project fitter, and I discussed it and he was going to talk to his office.
|
FIR12-00116
| INSP-Sprinkler Rough-in/Hydro | 6/19/2012 | 6/19/2012 | 6/19/2012 2:04:33 PM | P | PART |
|
|
24 hour air test started at 1:30 with 44 psi on the guage.
|
BLD11-01555
| FIRE-Final Inspection | 6/18/2012 | 6/19/2012 | 6/19/2012 12:42:06 PM | A | FAIL |
|
|
Need the project related fire alarm and fire sprinkler permits finaled. Also I found four smoke alarms on the second floor that need to be relocated to be more than the required 36" from the restroom door. The fire extinguishers need to have a current inspection tag as well.
|