Inspections for the day of: Tuesday, June 19, 2012.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00662 INSP-Alarm Testing6/19/20126/19/20126/19/2012 3:55:21 PMPPASS
East wing tamper valve for Shilo Sprinkler passed functional testing.
BLD12-01430 FIRE-Final Inspection6/18/20126/19/20126/19/2012 3:20:51 PMPPASS
life safety passed
FIR12-00161 INSP-Final Inspection6/19/20126/19/20126/19/2012 3:20:12 PMPFAIL
Todays inspection was for a building walk through. I found pendant heads blocked by lights in the third floor library. Pendant head bent in room 317. Pendants covered in rooms 328 and 316 and in the corridor closet outside of room 314. Three pendant heads are also covered in the area "A" south third floor corridor. The sidewall heads in the fourth floor exterior common balcony are located with the deflectors at 2 1/2" to 3" below the ceiling. Need verification they are listed for this. The first and second floors east of the fire wall has not been inspected yet since the light fixtures have not been installed yet. I did note that some of the corridor pendants in the two room apartments are located close to electrical boxes so if lights are installed obstruction may be present. Also washer and dryers are being installed in many of the closets in the residence rooms. The sprinkler pendants in these rooms are 155 degree which may not be high enough temperature. Tom, the project fitter, and I discussed it and he was going to talk to his office.
FIR12-00116 INSP-Sprinkler Rough-in/Hydro6/19/20126/19/20126/19/2012 2:04:33 PMPPART
24 hour air test started at 1:30 with 44 psi on the guage.
BLD11-01555 FIRE-Final Inspection6/18/20126/19/20126/19/2012 12:42:06 PMAFAIL
Need the project related fire alarm and fire sprinkler permits finaled. Also I found four smoke alarms on the second floor that need to be relocated to be more than the required 36" from the restroom door. The fire extinguishers need to have a current inspection tag as well.