Inspections for the day of: Wednesday, June 19, 2013.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01570 Electrical Rough-In6/19/20136/19/20136/19/2013 2:51:52 PMPPASS
ac unit outside west side of building Phone #: ###-#### >> Inspection requested via web by Andy Derrick ri ok, called contractor, he will see about receptacle within 25' of a/c units before final
ELE13-01546 Rough-In Permanent Service6/17/20136/19/20136/19/2013 2:40:02 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson ri ok, p/s u/g n ok
ELE13-01476 Electrical Rough-In6/19/20136/19/20136/19/2013 1:40:50 PMPPASS
underground - Max Phone #: ###-#### u/g ok for generator area
ELE13-01511 Final6/19/20136/19/20136/19/2013 1:04:00 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni ok final
ELE13-00419 Final6/19/20136/19/20136/19/2013 12:23:33 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Karl Paige ok final, signed card
ELE13-01305 Final6/18/20136/19/20136/19/2013 12:04:13 PMPNR
Final for kitchen remodel. Call Jimmy for questions. ###-#### Phone #: ###-#### >> Inspection requested via web by John Edwards met electrician, will recall
ELE13-01524 Rough-In Permanent Service6/14/20136/19/20136/19/2013 10:28:29 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
ELE13-01562 Electrical Rough-In6/18/20136/19/20136/19/2013 10:02:55 AMANR
graham Phone #: ###-#### Or Tammy ###-#### did conference, ri needs more work
ELE13-00734 Final6/18/20136/19/20136/19/2013 10:02:30 AMPCANC
Phone #: ###-#### >> Inspection requested via web by JOHN MCCURDY Inspection cancelled from web by: JOHN MCCURDY
ELE13-01562 Conference6/18/20136/19/20136/19/2013 9:50:30 AMADONE
graham Phone #: ###-#### Or Tammy ###-#### talked about 1 1/4", make-up, install boxes, tie grounds together in boxes, abandon ceiling heat,
ELE13-01567 Temporary Service6/18/20136/19/20136/19/2013 9:10:08 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE13-00853 Final6/18/20136/19/20136/19/2013 8:48:02 AMAPASS
Final inspection on 6 bollard fixtures. Please call Eric Hansen if any questions Phone #: ###-#### >> Inspection requested via web by brad williams ok final
ELE13-01564 Electrical Rough-In6/18/20136/19/20136/19/2013 8:17:45 AMAPASS
brandon Phone #: ###-#### ri ok
ELE13-01432 Permanent Service6/18/20136/19/20136/19/2013 8:03:10 AMAFAIL
Marcus Phone #: ###-#### called, left message, shall provide work space per NEC 110.26
ELE13-01499 Final6/18/20136/19/20136/19/2013 7:51:37 AMAFAIL
trench open Phone #: ###-#### >> Inspection requested via web by shane vigil called, NEC 300.5 shall bury cable 24", pvc 18"
ELE13-01477 Final6/19/20136/19/20136/19/2013 12:00:00 AMPCANC
Please call 30min prior for access - mitch Phone #: ###-####