ELE09-01599
| ELE-Aging Inspection | 6/19/2013 | 6/19/2013 | 6/27/2013 2:04:40 PM | | DONE |
|
|
still under construction
|
ELE13-01556
| Permanent Service | 6/19/2013 | 6/19/2013 | 6/19/2013 3:52:06 PM | P | FAIL |
|
|
Final on Service Phone #: ###-#### >> Inspection requested via web by Randy Fletcher NEC 110.26 Dedicated equipment space vent pipe under panel. stall indentify current carrying conductors NEC 408.4 circuit directory to brief
|
ELE13-01566
| Temporary Service | 6/19/2013 | 6/19/2013 | 6/19/2013 3:03:00 PM | P | PASS |
|
|
Temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI t/s u/g n ok
|
ELE13-01521
| Final | 6/19/2013 | 6/19/2013 | 6/19/2013 2:29:27 PM | P | FAIL |
|
|
warren Phone #: ###-#### Need ok seal in back of pump panel,support conduits below panel, install single ground rod.
|
ELE12-01799
| Permanent Service | 6/18/2013 | 6/19/2013 | 6/19/2013 2:12:02 PM | P | PASS |
|
|
Erik on site. Service inspection. Phone #: ###-#### >> Inspection requested via web by Clint Tate p/s u/g n ok
|
ELE13-01513
| Electrical Rough-In | 6/18/2013 | 6/19/2013 | 6/19/2013 1:35:43 PM | P | PASS |
|
|
walls Phone #: ###-#### >> Inspection requested via web by Kevin Burke rough-in ok cover walls
|
ELE13-00086
| Electrical Rough-In | 6/19/2013 | 6/19/2013 | 6/19/2013 1:09:07 PM | P | PASS |
|
|
2nd Floor wall cover. Dave is on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen rough-in ok cover 2nd floor wall of office 282/283/285
|
ELE13-01568
| Permanent Service | 6/19/2013 | 6/19/2013 | 6/19/2013 12:44:51 PM | A | PASS |
|
|
Service is next to the north east buildings that we just completed Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman p/s u/g n ok
|
ELE13-01569
| Temporary Service | 6/19/2013 | 6/19/2013 | 6/19/2013 12:33:24 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman t/s u/g n ok
|
ELE13-01525
| Final | 6/19/2013 | 6/19/2013 | 6/19/2013 10:51:51 AM | A | PASS |
|
|
job complete final ok
|
ELE13-01525
| Electrical Rough-In | 6/18/2013 | 6/19/2013 | 6/19/2013 10:48:28 AM | A | PASS |
|
|
robert Phone #: ###-#### correction completed rough-in ok
|
ELE13-00396
| Permanent Service | 6/18/2013 | 6/19/2013 | 6/19/2013 10:25:06 AM | A | FAIL |
|
|
or ###-#### Robert Phone #: ###-#### Utility power raiser to electrical meter has pulled apart. Install slip-joint, call back in for permanent service
|
ELE13-01206
| Final | 6/18/2013 | 6/19/2013 | 6/19/2013 10:08:59 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Inspection cancelled from web by: Cyndi Dale
|
ELE13-01540
| Temporary Service | 6/18/2013 | 6/19/2013 | 6/19/2013 10:05:01 AM | A | PASS |
|
|
temp pole, any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren t/p u/g n ok
|
ELE13-01561
| Permanent Service | 6/18/2013 | 6/19/2013 | 6/19/2013 9:50:14 AM | A | FAIL |
|
|
Richard Phone #: ###-#### NEC 230.24(B)(1) Vertical clearance for service-drop conductors. At the electrical service entrance to building,also at the lowest point of the drip loop of the building electrical entrance 10 ft. NEC 250.53(D)(2) Supplemental electrode required A metal underground water pipe shall be supplemented by an additional electrode
|
ELE13-01503
| Conference | 6/13/2013 | 6/19/2013 | 6/19/2013 9:08:44 AM | A | DONE |
|
|
Maria ###-####
|
ELE13-00001
| Final | 6/19/2013 | 6/19/2013 | 6/19/2013 8:40:40 AM | A | PASS |
|
|
garage code 1913 Phone #: ###-#### >> Inspection requested via web by Emmet Bushman final ok
|
ELE13-00217
| Final | 6/18/2013 | 6/19/2013 | 6/19/2013 8:40:06 AM | A | PASS |
|
|
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Joe Thomas final ok
|
ELE13-01552
| Electrical Rough-In | 6/17/2013 | 6/19/2013 | 6/18/2013 8:49:20 PM | P | CANC |
|
|
underground & bonding Phone #: ###-#### >> Inspection requested via web by Lars Johnson Inspection cancelled from web by: Lars Johnson
|