Inspections for the day of: Wednesday, June 19, 2013.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01599 ELE-Aging Inspection6/19/20136/19/20136/27/2013 2:04:40 PM DONE
still under construction
ELE13-01556 Permanent Service6/19/20136/19/20136/19/2013 3:52:06 PMPFAIL
Final on Service Phone #: ###-#### >> Inspection requested via web by Randy Fletcher NEC 110.26 Dedicated equipment space vent pipe under panel. stall indentify current carrying conductors NEC 408.4 circuit directory to brief
ELE13-01566 Temporary Service6/19/20136/19/20136/19/2013 3:03:00 PMPPASS
Temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI t/s u/g n ok
ELE13-01521 Final6/19/20136/19/20136/19/2013 2:29:27 PMPFAIL
warren Phone #: ###-#### Need ok seal in back of pump panel,support conduits below panel, install single ground rod.
ELE12-01799 Permanent Service6/18/20136/19/20136/19/2013 2:12:02 PMPPASS
Erik on site. Service inspection. Phone #: ###-#### >> Inspection requested via web by Clint Tate p/s u/g n ok
ELE13-01513 Electrical Rough-In6/18/20136/19/20136/19/2013 1:35:43 PMPPASS
walls Phone #: ###-#### >> Inspection requested via web by Kevin Burke rough-in ok cover walls
ELE13-00086 Electrical Rough-In6/19/20136/19/20136/19/2013 1:09:07 PMPPASS
2nd Floor wall cover. Dave is on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen rough-in ok cover 2nd floor wall of office 282/283/285
ELE13-01568 Permanent Service6/19/20136/19/20136/19/2013 12:44:51 PMAPASS
Service is next to the north east buildings that we just completed Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman p/s u/g n ok
ELE13-01569 Temporary Service6/19/20136/19/20136/19/2013 12:33:24 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman t/s u/g n ok
ELE13-01525 Final6/19/20136/19/20136/19/2013 10:51:51 AMAPASS
job complete final ok
ELE13-01525 Electrical Rough-In6/18/20136/19/20136/19/2013 10:48:28 AMAPASS
robert Phone #: ###-#### correction completed rough-in ok
ELE13-00396 Permanent Service6/18/20136/19/20136/19/2013 10:25:06 AMAFAIL
or ###-#### Robert Phone #: ###-#### Utility power raiser to electrical meter has pulled apart. Install slip-joint, call back in for permanent service
ELE13-01206 Final6/18/20136/19/20136/19/2013 10:08:59 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Inspection cancelled from web by: Cyndi Dale
ELE13-01540 Temporary Service6/18/20136/19/20136/19/2013 10:05:01 AMAPASS
temp pole, any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren t/p u/g n ok
ELE13-01561 Permanent Service6/18/20136/19/20136/19/2013 9:50:14 AMAFAIL
Richard Phone #: ###-#### NEC 230.24(B)(1) Vertical clearance for service-drop conductors. At the electrical service entrance to building,also at the lowest point of the drip loop of the building electrical entrance 10 ft. NEC 250.53(D)(2) Supplemental electrode required A metal underground water pipe shall be supplemented by an additional electrode
ELE13-01503 Conference6/13/20136/19/20136/19/2013 9:08:44 AMADONE
Maria ###-####
ELE13-00001 Final6/19/20136/19/20136/19/2013 8:40:40 AMAPASS
garage code 1913 Phone #: ###-#### >> Inspection requested via web by Emmet Bushman final ok
ELE13-00217 Final6/18/20136/19/20136/19/2013 8:40:06 AMAPASS
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Joe Thomas final ok
ELE13-01552 Electrical Rough-In6/17/20136/19/20136/18/2013 8:49:20 PMPCANC
underground & bonding Phone #: ###-#### >> Inspection requested via web by Lars Johnson Inspection cancelled from web by: Lars Johnson