ELE12-02558
| ELE-Aging Inspection | 6/19/2014 | 6/19/2014 | 6/19/2014 2:12:28 PM | | DONE |
|
|
see final
|
ELE12-02558
| Final | 6/19/2014 | 6/19/2014 | 6/19/2014 2:11:47 PM | P | PASS |
|
|
Temp. power only, electrical completed by other contractor and permit
|
ELE14-01602
| Final | 6/18/2014 | 6/19/2014 | 6/19/2014 1:56:47 PM | A | NR |
|
|
Wire cool ped receptacles. The cabinet is the one furthest west from the power pedestal. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell No access
|
ELE14-01602
| Electrical Rough-In | 6/18/2014 | 6/19/2014 | 6/19/2014 1:56:13 PM | A | NH |
|
|
Wire cool ped receptacles. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell No access
|
ELE14-00110
| Final | 6/19/2014 | 6/19/2014 | 6/19/2014 1:49:19 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI New smoke detectors shall not be powered by separate branch circuit, need to be tied to habitable living area
|
ELE14-01604
| Permanent Service | 6/19/2014 | 6/19/2014 | 6/19/2014 1:27:43 PM | A | PASS |
|
|
SE corner of Fairview & Fivemile, call Norm with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack p/s o/h n ok
|
ELE14-01604
| Electrical Rough-In | 6/19/2014 | 6/19/2014 | 6/19/2014 1:24:40 PM | P | FAIL |
|
|
SE corner of Fairview & Fivemile, call Norm with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Required dead front missing front service panel in vending trailer, NEC 400.5 Table Columm A 8 AWG ampacity 35 ampere for flexible cord. All 120 volt 15 and 20 ampere receptacles require GFCI protection
|
GCE14-00092
| GCE-Rough-In | 6/18/2014 | 6/19/2014 | 6/19/2014 10:49:58 AM | A | PASS |
|
|
CONTACT ###-#### FOR ACESS Bathroom addition rough-in ok cover walls
|
GCE13-00191
| GCE-Rough-In | 6/18/2014 | 6/19/2014 | 6/19/2014 10:47:53 AM | A | PASS |
|
|
Don ###-#### rough-in ok cover area 4B
|
GCE14-00091
| GCE-Final | 6/18/2014 | 6/19/2014 | 6/19/2014 9:42:52 AM | A | PASS |
|
|
(Mandatory Inspection)-Justing ###-#### final ok
|
GCE14-00091
| GCE-Rough-In | 6/19/2014 | 6/19/2014 | 6/19/2014 9:42:02 AM | A | PASS |
|
|
(Mandatory Inspection)-Justing ###-#### rough-in ok
|
ELE14-01404
| Electrical Rough-In | 6/18/2014 | 6/19/2014 | 6/19/2014 8:25:28 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Jonathan Poot correction done, rough-in ok cover patio room addition
|
ELE14-01602
| Electrical Rough-In | 6/18/2014 | 6/19/2014 | 6/18/2014 5:03:48 PM | A | CANC |
|
|
North side of Overland Rd. just west of S. Linda Vista Ave. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Inspection cancelled from web by: Dan Mitchell
|
ELE14-01602
| Final | 6/18/2014 | 6/19/2014 | 6/18/2014 5:03:46 PM | A | CANC |
|
|
North side of Overland Rd. just west of S. Linda Vista Ave. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Inspection cancelled from web by: Dan Mitchell
|