Inspections for the day of: Monday, June 19, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00844 Final6/19/20176/19/20176/20/2017 7:43:49 AMPFAIL
Phone #: ###-#### Inspection requested via web by Jason Wicks 406.12 All receps in a dwelling shall be Tamper resistan.( Island, cooktop, Up S.W bed next to door.) 410.16 B Open lamps shall not be installed in closet (Master, & front bed) 410.16 C Recessed light shall be 6in from front edge of closet shelf. (Down front bed) 210.8 All receps within 6ft of a sink shall be GFCI protected. (Washer) 110.7 Wireing shall be free of shorts.(Down Living room. 210.12 Dwelling bedrooms shall be AFCI protected. (Down bed) 314.20 Flush mounted boxes set back more than 1/4in. Back splash boxes shall be pulled out flush with tile. 210.52 A 2 Receps shall be within 6ft of a door. (Next to solid panel on rear slider) (Missing powder bath fan) (front down bed receps dead)
ELE17-00660 Final6/19/20176/19/20176/19/2017 2:54:13 PMPPASS
Mucho Phone #: ###-####-call for access code final ok
ELE17-00850 Final6/19/20176/19/20176/19/2017 1:26:02 PMPPASS
Joe Phone #: ###-#### Back patio final ok
ELE17-01901 Conference6/16/20176/19/20176/19/2017 1:07:41 PMPDONE
Will Phone #: ###-#### Laundry room/ Down bath remodel. Discussed wire support, Box fill, Tamper resit Receps, wet location rated can trim in shower
ELE17-01889 Temporary Service6/19/20176/19/20176/19/2017 10:46:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE17-01844 Temporary Service6/19/20176/19/20176/19/2017 10:46:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE17-00074 Electrical Rough-In6/16/20176/19/20176/19/2017 9:27:27 AMAPASS
Phone #: 2088413834 >> Inspection requested via mobile web by John Hinman Basement area only rough in ok
ELE17-01910 Electrical Rough-In6/16/20176/19/20176/19/2017 8:51:17 AMAPASS
For access please call John 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott Kitchen remodel, Living and bath is all fished in. Rough in ok to cover