Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00265 FIRE-Final Inspection6/19/20176/19/20176/19/2017 4:33:27 PMPPASS
No fire sprinkler modifications, fire alarm inspection is complete, fire extingiushers are in common area's with current inspection tags, door pull hardware is a special order, temporary hardware is installed until special order arrives. Final life fire safety inspection for area of work for this permit passed/complete.
FIR17-00245 INSP-Final Inspection6/16/20176/19/20176/19/2017 4:30:46 PMPPASS
Final fire alarm inspection for area of work associated with this permit passed/complete.
FIR17-00001 INSP-Sprinkler Rough-in6/19/20176/19/20176/19/2017 3:32:44 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
FIR17-00295 INSP-Sprinkler Rough-in6/19/20176/19/20176/19/2017 2:56:02 PMPPART
Rough to cover inspection complete for area of work, notated city approved drawings where heads will need to be added in common office area, all other area's approved for cover.
FIR17-00082 INSP-Sprinkler Rough-in6/16/20176/19/20176/19/2017 2:18:51 PMPPART
Partial rough to cover inspection complete, sprigs along east wall of gym are over 48 inches requiring bracing, reast of gym area approved for cover as noted on the city approved drawings.
FIR17-00246 INSP-Sprinkler Rough-in6/19/20176/19/20176/19/2017 2:16:29 PMPPASS
Previously noted items have been addressed, rough in inspection complete
BLD17-01128 FIRE-Final Inspection6/19/20176/19/20176/19/2017 11:32:08 AMAFAIL
Modifications need to be made to the fire sprinkler system to accomodate newly added equipment and roll up overhead door along the north wall. Storage racks exceed 8 feet in height, a racking permit is required for storage that exceeds 8 feet or the storage and racking needs to be lowered below 8 feet to the top of storage.
BLD17-01402 FIRE-Final Inspection6/16/20176/19/20176/19/2017 8:44:07 AMACANC
Called contact provided, Anna Phone #: ###-####, voicemail was not setup so no message could not be recorded. Tenant space was locked at time of arrival at 8:45AM to perform inspection. Life fire safety inspection request will need to be rescheduled.
BLD17-00585 FIRE-Final Inspection6/16/20176/19/20176/19/2017 8:15:47 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher will be mounted in discussed location. Final life fire safety inspection passed/complete.
FIR17-00165 INSP-Final Inspection6/14/20176/19/20176/19/2017 8:13:25 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00171 INSP-Final Inspection6/16/20176/19/20176/19/2017 8:12:55 AMAPASS
Final fire alarm inspection passed/complete
FIR17-00239 INSP-Final Inspection6/16/20176/19/20176/16/2017 12:36:20 PMACANC
Please contact Keith Orahood 30 min prior to Inspection start. ###-####

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank