Inspections for the day of: Tuesday, June 19, 2018.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02290 Rough-In Permanent Service6/19/20186/19/20186/19/2018 2:54:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Rough in ok cover p/s u/g n ok
ELE17-04353 Electrical Rough-In6/19/20186/19/20186/19/2018 2:30:08 PMPPASS
Job Foreman: Jay Karel Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
Listing confirmed. Rough in ok
ELE18-00184 Final6/19/20186/19/20186/19/2018 1:42:51 PMPPASS
For access please call Don 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott No card posted Final ok
ELE18-02200 Temporary Service6/18/20186/19/20186/19/2018 11:56:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE18-02285 Rough-In Permanent Service6/18/20186/19/20186/19/2018 11:41:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE18-02291 Electrical Rough-In6/19/20186/19/20186/19/2018 11:12:46 AMPCANC
Contact: Josh Mangum Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
ELE18-01433 Final6/18/20186/19/20186/19/2018 11:10:40 AMAPASS
Garage access code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE18-02249 Temporary Service6/18/20186/19/20186/19/2018 10:55:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Charles Davis
t/s u/g n ok
ELE18-02281 Temporary Service6/18/20186/19/20186/19/2018 10:44:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot
t/s u/g n ok
ELE18-02277 Temporary Service6/18/20186/19/20186/19/2018 10:43:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot
t/s u/g n ok
ESC18-00193 Random Inspection6/19/20186/19/20186/19/2018 10:43:00 AMPFAIL
Inlets to north of lots no protection. Will check 6-26-18 for completion.
ELE18-02282 Temporary Service6/18/20186/19/20186/19/2018 10:27:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot
t/s u/g n ok
ELE18-01775 Electrical Rough-In6/18/20186/19/20186/19/2018 10:16:56 AMAPASS
Remaining underground for swimming pool Phone #: ###-#### Inspection requested via web by Lars Johnson
Rough in ok cover
ELE18-01513 Electrical Rough-In6/18/20186/19/20186/19/2018 10:03:58 AMAPASS
Swimming pool/spa EQ bonding plane wiring ; connections Phone #: ###-#### Inspection requested via web by Lars Johnson
EQ bond pool and hot tub rough in ok cover
ELE18-02290 Rough-In Permanent Service6/18/20186/19/20186/19/2018 9:47:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
110.3- Unable to confirm listing for non-metallic pancake boxes on exterior. Provde documentation.
210.52- A receptacle outlet shall be located with in 6' of flex room door to patio. nearest one 8'.
300.4 (A)(1)- Cables passing thru holes that do not meaintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Marked with X.
300.4 (B)(1)- Where NM cable enter fireplace it shall be protected by a bushd fitting.
300.4(G)- Where #4 or larger enter an enclosure they shall enter thru a bushed fitting.
Check smoke detector locations, unable to locate print to confirm.
complete make-up, fireplace switches, wirenuts missing switch near office stair.