Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01975 Electrical Rough-In6/17/20206/19/20206/19/2020 4:01:51 PMPFAIL
Screened- Bart Phone #: ###-#### 210.52(A)- Upstairs walls 2' or wider shall have receptacle outlets installed. 210.52(G)- All patios and decks shall have a receptacle outlet installed within its perimeter. 210.70- Each man door with grade level exterior access shall have an exterior light installed. 250.24- Grounding electrode shall bond grounded conductor in the main service disconnect and an equipment ground installed from service to sub-panel. 250.64- Connection to grounding electrode shall remain accessible. 300.4- Walk house for additional nail plates. 314.25- Complete cans and install all covers. * Empty smoke box in down front rm.
ELE20-00206 Final6/18/20206/19/20206/19/2020 2:27:51 PMPFAIL
Code for front door is 5481 Don''t shoot the messenger I stopped in their last night to hang the last 2 lights that were on back order and they Statered staging the house for a photo shoot let me know how you feel about that. Phone #: ###-#### Inspection requested via web by David Kubik 250.94- Intersystem bond shall be provided for utiities. 426.28- Ice melting heat tape shall have GFED protection. Equipment protective device shall be installed at circuit supply.
Unable to test garage due to materials cover devices. Panel in basement to left of mechanical door.
ELE20-01028 Final6/18/20206/19/20206/19/2020 2:20:14 PMPPASS
thank you sir. Call with any questions Phone #: ###-#### Inspection requested via web by David Kubik Floor heat only final ok
ELE20-02091 Permanent Service6/19/20206/19/20206/19/2020 1:36:13 PMPFAIL
access at North gate Phone #: ###-#### Inspection requested via web by David Nelson 230.28(B)- Point of attachment of overhead service conductor shall not be above a coupling above last point of securement. Coupling in upper soffit above last strap.
ELE20-02078 Permanent Service6/18/20206/19/20206/19/2020 10:42:27 AMAPASS
Justin is contact Phone #: ###-#### Inspection requested via web by Lori Stout Located facing federal way. Available fault current to be posted by final. p/s u/g n ok
ELE20-00808 Permanent Service6/18/20206/19/20206/19/2020 10:41:49 AMAPASS
JUSTIN IS CONTACT Phone #: ###-#### Inspection requested via web by Lori Stout Located facing federal way. Available fault current to be posted by final. p/s u/g n ok
ELE20-02078 Electrical Rough-In6/18/20206/19/20206/19/2020 10:33:14 AMAPASS
Justin is contact Phone #: ###-#### Inspection requested via web by Lori Stout Public work underground and pole bases rough in ok cover.
ELE20-00808 Electrical Rough-In6/18/20206/19/20206/19/2020 10:31:49 AMAPASS
Justin is contact Phone #: ###-#### Inspection requested via web by Lori Stout
Public works underground and pole bases Rough in ok cover
ELE20-02037 Temporary Service6/18/20206/19/20206/19/2020 9:19:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE20-01995 Temporary Service6/18/20206/19/20206/19/2020 9:19:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok