Inspections for the day of: Friday, June 19, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD20-01075 FIRE-Conference6/18/20206/19/20206/19/2020 1:21:37 PMPCANC
Conference cancelled per conversation with point of contact, will be rescheduled for a later date.

Phone #: ###-#### Inspection requested via web by James Ressler
BLD19-04395 FIRE-Final Inspection6/17/20206/19/20206/19/2020 11:50:43 AMAFAIL
Provide city approved paperwork as discussed. Mount fire extinguishers as discussed. Provide annual inspection for fire sprinkler system. Re-attach sprinkler hangers that have came loose under overhead door.

Screened- John Phone #: ###-####
FIR20-00257 INSP-Sprinkler Rough-in6/19/20206/19/20206/19/2020 11:12:22 AMADONE
Fire pump commissioning complete.
FIR20-00257 INSP-Sprinkler Rough-in6/19/20206/19/20206/19/2020 11:11:23 AMPFAIL
Correct sway bracing as discussed.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00075 INSP-Final Inspection6/19/20206/19/20206/19/2020 11:10:26 AMPCANC
Final fire sprinkler inspection cancelled per conversation with point of contact, irrigation shutdown on flow switch activation not installed, inspection will be rescheduled for a later date.

Ready any time, call James before heading up Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00075 INSP-Sprinkler Rough-in/Hydro6/19/20206/19/20206/19/2020 11:09:19 AMPDONE
Hydrostatic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.

Overhead Hydro before Final, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00888 INSP-Final Inspection6/18/20206/19/20206/19/2020 10:27:08 AMPPASS
Final inspection for underground supply complete.

Jeff Chaney is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00888 INSP-Sprinkler Rough-in6/18/20206/19/20206/19/2020 10:27:08 AMAFAIL
Wrong permit requested for type of inspection.

This is a Fire Pump Final. Contact is Jeff Chaney Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00888 INSP-Final Inspection6/18/20206/19/20206/18/2020 1:15:47 PMACANC
The contact is Jeff Chaney. Have a good day!! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus