Inspections for the day of: Monday, June 2, 2003.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01000 ELE-Aging Inspection6/2/20036/2/20036/2/2003 12:00:00 AM PART
wsuc 6/2/2003 1:00:12 PM
ELE02-01001 ELE-Aging Inspection6/2/20036/2/20036/2/2003 12:00:00 AM PART
wsuc 6/2/2003 1:00:26 PM
ELE03-01555 Permanent Service5/28/20036/2/20036/2/2003 12:00:00 AMAFAIL
###-#### cor. posted called 250.92(A)(3), 250.66,52(A)(1),104(A)(1) needs #4 G.E.C. for grd or bond too water system, 250.24(A)(1) terminate G.E.C. too neutral bus, 230.24(A) needs 8f over roof , 250.53(B) grd rods shall be 6ft or more apart 6/2/2003 10:34:18 AM
ELE03-00398 Electrical Rough-In5/28/20036/2/20036/2/2003 12:00:00 AMAPART
bud ; Phone #: ###-#### Internet Inspection Request from: Annette Moore 4 rms see print 6/2/2003 9:19:14 AM
ELE02-02684 Electrical Rough-In5/30/20036/2/20036/2/2003 12:00:00 AMAPART
ernest ; Phone #: ###-#### Internet Inspection Request from: Annette Moore u/g ok
6/2/2003 9:18:39 AM
ELE03-01519 Temporary Service5/30/20036/2/20036/2/2003 12:00:00 AMAPASS
RON; Phone #: ###-#### Internet Inspection Request from: Darla Downs
t/s o/h new ok 6/2/2003 11:02:33 AM
ELE03-01515 Permanent Service5/30/20036/2/20036/2/2003 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Andy Rose
p/s o/h rec. ok 6/2/2003 9:50:53 AM
ELE02-03774 Final5/28/20036/2/20036/2/2003 12:00:00 AMPPASS
terry; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 6/2/2003 2:28:16 PM
ELE03-00057 Electrical Rough-In6/2/20036/2/20036/2/2003 12:00:00 AMPPART
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore N,S,W, soffit lights ok 6/2/2003 4:24:03 PM
ELE03-01250 Final6/2/20036/2/20036/2/2003 12:00:00 AMPNH
gary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore nalc called 6/2/2003 1:39:32 PM
ELE01-02198 Final6/2/20036/2/20036/2/2003 12:00:00 AMPCANC
###-#### sherie
ELE01-02198 Electrical Rough-In6/2/20036/2/20036/2/2003 12:00:00 AMPPASS
sherrie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 6/2/2003 3:30:36 PM
ELE03-01570 Rough-In Permanent Service6/2/20036/2/20036/2/2003 12:00:00 AMPPASS
INGRID; Phone #: ###-#### Internet Inspection Request from: Darla Downs r/i ok
p/s o/h rec. ok 6/2/2003 2:46:36 PM
ELE03-01452 Electrical Rough-In6/2/20036/2/20036/2/2003 12:00:00 AMPPASS
###-#### installed range recep 6/2/2003 12:27:49 PM