ELE02-01000
| ELE-Aging Inspection | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | | PART |
|
|
wsuc 6/2/2003 1:00:12 PM
|
ELE02-01001
| ELE-Aging Inspection | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | | PART |
|
|
wsuc 6/2/2003 1:00:26 PM
|
ELE03-01555
| Permanent Service | 5/28/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | A | FAIL |
|
|
###-#### cor. posted called 250.92(A)(3), 250.66,52(A)(1),104(A)(1) needs #4 G.E.C. for grd or bond too water system, 250.24(A)(1) terminate G.E.C. too neutral bus, 230.24(A) needs 8f over roof , 250.53(B) grd rods shall be 6ft or more apart 6/2/2003 10:34:18 AM
|
ELE03-00398
| Electrical Rough-In | 5/28/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | A | PART |
|
|
bud ; Phone #: ###-#### Internet Inspection Request from: Annette Moore 4 rms see print 6/2/2003 9:19:14 AM
|
ELE02-02684
| Electrical Rough-In | 5/30/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | A | PART |
|
|
ernest ; Phone #: ###-#### Internet Inspection Request from: Annette Moore u/g ok
6/2/2003 9:18:39 AM
|
ELE03-01519
| Temporary Service | 5/30/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | A | PASS |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Darla Downs
t/s o/h new ok 6/2/2003 11:02:33 AM
|
ELE03-01515
| Permanent Service | 5/30/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Andy Rose
p/s o/h rec. ok 6/2/2003 9:50:53 AM
|
ELE02-03774
| Final | 5/28/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | PASS |
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 6/2/2003 2:28:16 PM
|
ELE03-00057
| Electrical Rough-In | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | PART |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore N,S,W, soffit lights ok 6/2/2003 4:24:03 PM
|
ELE03-01250
| Final | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | NH |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore nalc called 6/2/2003 1:39:32 PM
|
ELE01-02198
| Final | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | CANC |
|
|
###-#### sherie
|
ELE01-02198
| Electrical Rough-In | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | PASS |
|
|
sherrie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 6/2/2003 3:30:36 PM
|
ELE03-01570
| Rough-In Permanent Service | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | PASS |
|
|
INGRID; Phone #: ###-#### Internet Inspection Request from: Darla Downs r/i ok
p/s o/h rec. ok 6/2/2003 2:46:36 PM
|
ELE03-01452
| Electrical Rough-In | 6/2/2003 | 6/2/2003 | 6/2/2003 12:00:00 AM | P | PASS |
|
|
###-#### installed range recep 6/2/2003 12:27:49 PM
|