FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 6/2/2006 | 6/2/2006 | 6/5/2006 9:19:21 AM | P | FAIL |
|
|
Overhead inspection performed for the 1st floor hard lid soffit areas at the hotel lobby-some areas are overspaced, heads not roughed in as shown on plans, be aware of obstructions by adjacent soffits to to higher drop ceiling areas. Also inspected the 9th floor rough-in, installation appears acceptable except for the west main which is still concealed by sheetrock lids- this area will need to be exposed for inspection before approval for cover can be granted for the 9th floor.
|
FIR06-00274
| INSP-Sprinkler Rough-in/Hydro | 6/2/2006 | 6/2/2006 | 6/2/2006 4:01:21 PM | P | PASS |
|
|
Corrections have been made, fire sprinkler work passed inspection, okay to final.
|
BLD06-00213
| FIRE-Final Inspection | 6/2/2006 | 6/2/2006 | 6/2/2006 3:53:34 PM | P | FAIL |
|
|
Some items on the previous correction notice have been completed, however the new duct smoke detectors installed at two locations are not connected to the building fire alarm system as required. This work will require a fire alarm permit to be issued prior to installation. Also need to provide proof of a current annual inspection by a qualified fire sprinkler contractor on the building sprinkler system.
|
FIR05-00738
| INSP-Sprinkler Rough-in/Hydro | 6/1/2006 | 6/2/2006 | 6/2/2006 1:51:35 PM | A | PART |
|
|
UG hydrostatic test and overhead hydrostatic test for the two AG systems performed satisfactory.
|
FIR06-00337
| INSP-Alarm Testing | 6/1/2006 | 6/2/2006 | 6/2/2006 1:49:34 PM | A | CANC |
|
|
This inspection request was mistakenly called in under the wrong permit number by the customer, was intended for FIR06-00377.
|
BLD06-00825
| FIRE-Final Inspection | 6/1/2006 | 6/2/2006 | 6/2/2006 11:04:43 AM | A | PASS |
|
|
Required correction is complete, fire life safety inspection passed.
|
FIR06-00382
| INSP-Conference | 6/2/2006 | 6/2/2006 | 6/2/2006 10:58:25 AM | P | DONE |
|
|
On site confrence to discuss duct smoke detection in the existing ductwork.
|
BLD06-00213
| FIRE-Final Inspection | 6/2/2006 | 6/2/2006 | 6/2/2006 10:27:54 AM | A | FAIL |
|
|
Missing required fire extinguisher, need to repair non-functional emergency light above the main entry, provide approved door hardware at the main entry/exit and the back door (remove manual thumbturns, door knob), provide signage above main entry/exit, provide means to test the two duct smoke detectors.
|
FIR06-00296
| INSP-Final Inspection | 6/1/2006 | 6/2/2006 | 6/2/2006 10:23:09 AM | A | FAIL |
|
|
Ceiling tile at several locations is not installed, missing escutcheons at several areas.
|