Inspections for the day of: Friday, June 2, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00425 INSP-Sprinkler Rough-in/Hydro6/2/20066/2/20066/5/2006 9:19:21 AMPFAIL
Overhead inspection performed for the 1st floor hard lid soffit areas at the hotel lobby-some areas are overspaced, heads not roughed in as shown on plans, be aware of obstructions by adjacent soffits to to higher drop ceiling areas. Also inspected the 9th floor rough-in, installation appears acceptable except for the west main which is still concealed by sheetrock lids- this area will need to be exposed for inspection before approval for cover can be granted for the 9th floor.
FIR06-00274 INSP-Sprinkler Rough-in/Hydro6/2/20066/2/20066/2/2006 4:01:21 PMPPASS
Corrections have been made, fire sprinkler work passed inspection, okay to final.
BLD06-00213 FIRE-Final Inspection6/2/20066/2/20066/2/2006 3:53:34 PMPFAIL
Some items on the previous correction notice have been completed, however the new duct smoke detectors installed at two locations are not connected to the building fire alarm system as required. This work will require a fire alarm permit to be issued prior to installation. Also need to provide proof of a current annual inspection by a qualified fire sprinkler contractor on the building sprinkler system.
FIR05-00738 INSP-Sprinkler Rough-in/Hydro6/1/20066/2/20066/2/2006 1:51:35 PMAPART
UG hydrostatic test and overhead hydrostatic test for the two AG systems performed satisfactory.
FIR06-00337 INSP-Alarm Testing6/1/20066/2/20066/2/2006 1:49:34 PMACANC
This inspection request was mistakenly called in under the wrong permit number by the customer, was intended for FIR06-00377.
BLD06-00825 FIRE-Final Inspection6/1/20066/2/20066/2/2006 11:04:43 AMAPASS
Required correction is complete, fire life safety inspection passed.
FIR06-00382 INSP-Conference6/2/20066/2/20066/2/2006 10:58:25 AMPDONE
On site confrence to discuss duct smoke detection in the existing ductwork.
BLD06-00213 FIRE-Final Inspection6/2/20066/2/20066/2/2006 10:27:54 AMAFAIL
Missing required fire extinguisher, need to repair non-functional emergency light above the main entry, provide approved door hardware at the main entry/exit and the back door (remove manual thumbturns, door knob), provide signage above main entry/exit, provide means to test the two duct smoke detectors.
FIR06-00296 INSP-Final Inspection6/1/20066/2/20066/2/2006 10:23:09 AMAFAIL
Ceiling tile at several locations is not installed, missing escutcheons at several areas.