BLD07-00143
| FIRE-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 4:21:20 PM | P | FAIL |
|
|
Provide the missing exit sign in the daycare room and repair the inoperative exit sign in the daycare. Provide an additional emergency light in the multipurpose room as discussed. Will also need the door hardware verified at the final inspection after it has been installed.
|
FIR08-00308
| INSP-Final Inspection | 6/2/2008 | 6/2/2008 | 6/2/2008 4:19:08 PM | P | PART |
|
|
A temporary occupancy is being given until the remaining appliances have been installed and verified.
|
BLD07-02212
| FIRE-Final Inspection | 6/2/2008 | 6/2/2008 | 6/2/2008 2:59:04 PM | P | PASS |
|
|
life safety passed
|
FIR08-00180
| INSP-Final Inspection | 6/2/2008 | 6/2/2008 | 6/2/2008 2:57:38 PM | P | PASS |
|
|
Permit finaled.
|
BLD08-00973
| FIRE-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 2:56:59 PM | A | FAIL |
|
|
See the correction notice for the items needing addressed
|
BLD07-02914
| FIRE-Final Inspection | 5/29/2008 | 6/2/2008 | 6/2/2008 12:38:57 PM | P | PASS |
|
|
fire life safety passed
|
FIR08-00094
| FIR-Aging Inspection | 6/2/2008 | 6/2/2008 | 6/2/2008 11:31:42 AM | | NR |
|
|
work is in progress
|
BLD07-03193
| FIRE-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 11:30:57 AM | P | CANC |
|
|
Paving was not complete which affected the fire dept access. Inspection to be rescheduled for wednesday.
|
FIR07-00663
| INSP-Sprinkler Rough-in | 5/29/2008 | 6/2/2008 | 6/2/2008 10:32:11 AM | A | PASS |
|
|
UG Flush and the forward flush passed.. I notified todd that the flow switch and tamper switches will need to be connected to the fire alarm system.
|
FIR08-00293
| INSP-Sprinkler Rough-in | 5/30/2008 | 6/2/2008 | 6/2/2008 9:51:15 AM | A | PASS |
|
|
The underground supply piping is ok to bury.
|
BLD07-02689
| FIRE-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 9:16:49 AM | A | FAIL |
|
|
Project is not ready for inspection. Ceiling tile is missing throughout the entire facility. Exit signs and emergency lights were being repaired/installed while I was there. Occupant load signs had not been addressed yet as well.
|
BLD07-02067
| FIRE-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 8:49:26 AM | P | CANC |
|
|
kevin - fire life safety Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|
FIR07-01013
| INSP-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 12:00:00 AM | A | CANC |
|
|
Jeremiah, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
FIR07-00999
| INSP-Alarm Testing | 5/30/2008 | 6/2/2008 | 6/2/2008 12:00:00 AM | A | CANC |
|
|
Matt; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
FIR07-00998
| INSP-Alarm Testing | 5/30/2008 | 6/2/2008 | 6/2/2008 12:00:00 AM | P | CANC |
|
|
Matt; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|