FIR03-00411
| FIR-Aging Inspection | 6/2/2010 | 6/2/2010 | 6/10/2010 12:57:43 PM | | DONE |
|
|
Set to expire
|
FIR03-00230
| FIR-Aging Inspection | 6/2/2010 | 6/2/2010 | 6/3/2010 2:44:00 PM | | DONE |
|
|
Site visit scheduled.
|
FIR03-00397
| FIR-Aging Inspection | 6/2/2010 | 6/2/2010 | 6/2/2010 5:38:03 PM | | DONE |
|
|
Set to expire
|
FIR10-00061
| INSP-Final Inspection | 5/28/2010 | 6/2/2010 | 6/2/2010 5:34:55 PM | A | FAIL |
|
|
Items not repaired and included on the original inspection correction list include the duct detector at "Taters", missing signage at the door to the FACP room, sprinkler tamper switch must report as a supervisory condition. Also noted a trouble on the panel at one beam detector, overspaced and missing notification at the mechanical mezzanine, walkthrough completed for area B. Attempted an expedited test of the building alarm notification circuts by providing an additional inspector on site- test failed due to non-functional voice evacuation speakers at the main convention hall. A re-inspection fee will apply to the next site visit, see permit conditions for details.
|
FIR06-00362
| INSP-Final Inspection | 6/2/2010 | 6/2/2010 | 6/2/2010 5:11:22 PM | P | PASS |
|
|
Permit okay for final status.
|
FIR10-00165
| INSP-Sprinkler Rough-in | 6/2/2010 | 6/2/2010 | 6/2/2010 5:05:07 PM | P | FAIL |
|
|
Correction items include one obstructed head at room 205 first floor, sheetmetal impingement at a branchline in the hallway first floor, beam obstruction at the basement, overspaced head under the stairway to the basement, noted field modifications to be shown on plans including relocated branchlines and dry sw feeds. See plan annotations for locations marked today.
|
FIR09-00645
| INSP-Final Inspection | 6/1/2010 | 6/2/2010 | 6/2/2010 8:57:44 AM | A | CANC |
|
|
it is best for customer to have testing done at 9 AM
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
|
FIR09-00643
| INSP-Final Inspection | 6/1/2010 | 6/2/2010 | 6/2/2010 8:57:31 AM | A | CANC |
|
|
it is best for customer to have testing done at 9 AM
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
|