Inspections for the day of: Wednesday, June 2, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00411 FIR-Aging Inspection6/2/20106/2/20106/10/2010 12:57:43 PM DONE
Set to expire
FIR03-00230 FIR-Aging Inspection6/2/20106/2/20106/3/2010 2:44:00 PM DONE
Site visit scheduled.
FIR03-00397 FIR-Aging Inspection6/2/20106/2/20106/2/2010 5:38:03 PM DONE
Set to expire
FIR10-00061 INSP-Final Inspection5/28/20106/2/20106/2/2010 5:34:55 PMAFAIL
Items not repaired and included on the original inspection correction list include the duct detector at "Taters", missing signage at the door to the FACP room, sprinkler tamper switch must report as a supervisory condition. Also noted a trouble on the panel at one beam detector, overspaced and missing notification at the mechanical mezzanine, walkthrough completed for area B. Attempted an expedited test of the building alarm notification circuts by providing an additional inspector on site- test failed due to non-functional voice evacuation speakers at the main convention hall. A re-inspection fee will apply to the next site visit, see permit conditions for details.
FIR06-00362 INSP-Final Inspection6/2/20106/2/20106/2/2010 5:11:22 PMPPASS
Permit okay for final status.
FIR10-00165 INSP-Sprinkler Rough-in6/2/20106/2/20106/2/2010 5:05:07 PMPFAIL
Correction items include one obstructed head at room 205 first floor, sheetmetal impingement at a branchline in the hallway first floor, beam obstruction at the basement, overspaced head under the stairway to the basement, noted field modifications to be shown on plans including relocated branchlines and dry sw feeds. See plan annotations for locations marked today.
FIR09-00645 INSP-Final Inspection6/1/20106/2/20106/2/2010 8:57:44 AMACANC
it is best for customer to have testing done at 9 AM
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
FIR09-00643 INSP-Final Inspection6/1/20106/2/20106/2/2010 8:57:31 AMACANC
it is best for customer to have testing done at 9 AM
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner